Fig. 5: Conversion of the supply air connection
3
2
2
1
1
3
A
B
Side supply air connection (A)
1. Remove lower rear wall (2) of the EuroCondense three
2. Loosen screws and remove the cover plate (1)
3. Remove the intake pipe leading upward from the intake pipe elbow (3)
4. Turn intake pipe elbow (3) into the side position
5. Mount lower rear wall (2)
Rear supply air connection (B)
1. Remove lower rear wall (3) of the EuroCondense three
2. Take out cover plate (2) from lower rear wall (3)
3. Remove the intake pipe leading upward with intake pipe elbow
4. Mount straight intake pipe (1)
5. Mount lower rear wall (3)
Before installation
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
17