Separate circuit
(5736)
The DHW separate circuit can only be used in a boiler cascade.
-
Off
: The DHW separate circuit is switched off. Each available boiler can feed the
DHW storage tank.
-
On
: The DHW separate circuit is switched on. The DHW charging is only done
from the boiler defined for this.
For a DHW separate circuit, under prog. no. 5731, the DHW control element Q3 is
set on "diverting valve“.
Optg action DHW div valve
(5737)
Using this parameter the diverting valve position is set, which applies during ac-
tive output.
-
Position on DHW
: during active output the diverting valve is in the DHW posi-
tion.
-
Position on heating circuit
: during active output the diverting valve is in the
heating circuit position.
Ctrl boiler pump/DHW valve
(5774)
With this parameter it can be defined for special hydraulic systems that the boiler
pump Q1 and the diverting valve Q3 only are responsible for DHW and heating
circuit 1, however not for heating circuits 2 and 3 or for the external consumer
circuit.
-
All requests
: the diverting valve is connected hydraulically for all requests and
switches between DHW mode and the remaining requests. The boiler pump
runs for all requests.
-
Request HC1/DHW only
: The diverting valve is connected hydraulically only for
heating circuit 1 and DHW and switches between DHW mode and heat circuit 1
mode. All other requests are not connected hydraulically via the diverting valve
(DV) and the boiler pump, but rather directly connected to the boiler.
Solar controlling element
(5840)
The solar heating system can also be operated with charging pumps instead of
with a collector pump and diverting valves for the storage tank connection.
-
Charge pump
: When using with the charging pump all exchangers can be flow-
ed through simultaneously. The parallel or alternative mode is possible.
-
Deflecting valve
: When using with a diverting valve always only one exchanger
can be flowed through. Only the alternative mode is possible.
External solar exchanger
(5841)
For solar schemes with two storage connections it must be set whether the exter-
nal heat exchanger is present and is used
together
for DHW and buffer storage or
only
for one of the two
.
Combined storage
(5870)
Combined storage-specific functions will be activated with this setting. For in-
stance, the buffer storage electric heater insert can be used for heating as well as
for DHW.
-
No
: No combined storage exists.
-
Yes
: A combined storage exists.
Relay outputs QX1 - QX3 (5890 bis 5892)
Relay outputs QX1/QX2/QX3
(5890 bis 5892)
-
None
: Relay outputs deactivated.
-
Circulation pump Q4
: The connected pump serves as domestic hot water circu-
lation pump (see prog. no. 1660).
Programming
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
109
Содержание EC three 125
Страница 25: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 25 ...
Страница 27: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 27 ...
Страница 29: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 29 ...
Страница 33: ...4 8 Legend Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 33 ...
Страница 147: ...Space for notes 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 147 ...