9.7 Check and replacing
ionisation electrode
The ionisation electrode must always be in contact with the flame. During burner
operation, the measured ionisation flow must following data display:
- At minimum power > 5 µA DC (switching threshold at 0.7 µA DC)
- At maximum power > 10 µA DC
Measurement ionization current
For measurement of the ionisation current, pull plug from the gas-firing autom-
aton and connect amperemeter between plug and electrode.
Danger of electric shock!
Do not touch plug contacts during the ignition process!
Changing the ionisation electrode
Danger of electric shock!
Before performing service work, power to the boiler must
be shut off and it must be secured from accidentally being switched back on!
Fig. 37: Removing ionisation electrode
1
2
Eurocondense three
215 - 300
Eurocondense three
125 - 170
1
2
1. Release ionisation line
2. Remove nuts and pull out the ionisation electrode (1) with the seal (2)
3. Insert the new ionisation electrode with seal and fasten with nuts
Note: Installation position and electrode clearance has to be maintained according
to
Fig. 38
4. Reconnect the ionisation line
Maintenance
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
135
Содержание EC three 125
Страница 25: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 25 ...
Страница 27: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 27 ...
Страница 29: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 29 ...
Страница 33: ...4 8 Legend Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 33 ...
Страница 147: ...Space for notes 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 147 ...