Automatic operation
Auto
:
- Heating operation according to time programme
- Nominal temperature values comfort or reduced according to time pro-
gramme
- Protection functions (plant frost protection, overheating protection) activated
- Automatic summer/winter switch-over (automatic switching over between
heating and summer operation from a certain outside temperature)
- Automatic day heating limit (automatic change-over between heating and sum-
mer operation, if outside temperature exceeds the nominal room value)
Continuous Operation
comfort or
reduced
:
- Heating operation without time programme
- Protection functions activated
- Automatic summer/winter switch-over is not activated
- Automatic day heating limit is not activated
Protection operation
:
- No heating operation
- Temperature according to frost protection setpoint
- Protection functions activated
- Automatic summer/winter switch-over is not activated
- Automatic day heating limit is not activated
- DHW operation according to status
7.4 Stop drinking water
operation
Stop drinking water operation
xxxxxxxxxxxxxx
-
Switched on
Drinking water will be prepared according to the selected switching
programme.
-
Switched off
Drinking water preparation has been de-activated.
Note: Legionella function
Each Sunday during the first charge of the DHW tank, the legionella function is ac-
tivated; this means the DHW ist being heated up to 65 °C once for eliminating the
existing legionellas.
7.5 Setting room setpoint
Setting
comfort setpoint:
1. Set comfort setpoint with the control knob
=> The value will automatically be take over
Operation
46
Condensing gas boiler Eurocondense three125-300 kW
7308536-02 06.13
Содержание EC three 125
Страница 25: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 25 ...
Страница 27: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 27 ...
Страница 29: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 29 ...
Страница 33: ...4 8 Legend Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 33 ...
Страница 147: ...Space for notes 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 147 ...