Installation, user and maintenance manual
– GAHP-A
71
5. In the case of replacement, before re-mounting the new thermostat, spread an
adequate quantity of thermal grease on the lower part of the thermostat in order
to ensure correct heat conductivity;
6. Re-connect the cables to the two connectors, paying attention to cover the contacts
completely with the two red silicone protections;
7. Re-mount the front panel of the unit.
Figure 8.3
– Inspection of generator limit thermostat
Thermostat detail
Figure 8.4
– Safety valve kit
Necessary components
LEGEND
n.1 Safety valve
n.1 O Ring
n.1 Litmus test
The components subject of the intervention are represented in Figure 8.5 particular
safety valve mounted on unit on page 72.