54
How to connect the plant water circulation pump
For how to connect the system pumps, see the section with this title in Section 5.3 TYPE
B (DDC) on page 41.
5.5
HOW TO REMOTELY FLAME CONTROLLER RESET
The fl ame controller reset can be controlled remotely by installing a button (not supplied)
to the fl ame controller inside the unit’s electrical panel.
Connect the button as instructed below.
You will need
: the appliance disconnected from the electricity supply
1. The cable required to connect the reset button must be 3x0.75mm
2
.
2. Cut a suitable length of cable.
3. Connect the cable to the blind terminals A (see Figure 5.18 Button connection for
fl ame controller reset on page 55).
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the
cabling carefully before powering the unit.