![Potterton A-Cubed Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/potterton/a-cubed/a-cubed_installation-user-and-maintenance-manual_1583175020.webp)
20
Reset appliance controller
The Table 3.3 Menu 2 on page 20 shows the actions available in menu 2.
For regulatory reasons, the fl ame controller reset is in a dedicated voice of menu.
Table 3.3
– Menu 2
ACTION
REQUIRED FOR EXECUTION
SHOWN ON DISPLAY AS
20
Reset fl ame controller arrest
2. 20
21
Reset other operating codes
2. 21
22
Manual defrost
2. 22
23
Timed forcing to minimum power
2. 23
24
Timed forcing to maximum power
2. 24
25
Regulation of power
2. 25
E
(EXIT MENU)
2. E
The general operating codes of the controller can be reset with functions "20" and "21".
ctions "23", "24" and "25" are used to regulate the combustion parameters or for gas
type changeovers, and are thus for use only by the installation technician or Potterton
Commercial Technical Department (for other information refer to Section 6.1 PROCEDURE
FOR INITIAL ACTIVATION on page 57).
ACTION "20
Reset fl ame controller arrest; this may be used when the appliance is fi rst activated,
see Section 3.1 START UP (AND SHUT DOWN) on page 15, when the appliance is in a
permanent locked condition or after a long period of disuse (see Section 3.5 PROLONGED
PERIODS OF DISUSE on page 22).
You will need:
access to the electrical panel, see Section "Display and knob".
To reset the fl ame control unit select menu 2, as indicated in the Section "Accessing the
Menus"; then proceed as follows:
1. The display shows: "2." Press the knob to access the menu. The display initially
shows item "2. 20".
2. Press the knob to display the fl ashing reset request: "reS1".
3. Press the knob again to reset the fl ame controller. The reset request stops fl ashing,
and again the display shows "2. 20". The reset operation has been performed.
4. To quit the menu, turn the knob clockwise until the "2. E" is displayed. Now press
the knob to return to menu selection: "2.".
5. To exit the menu selection and return to the normal visualisation of the parameters
of the appliance, turn the knob clockwise until "E" displays; press the knob to quit.
ACTION "21"
Reset other warnings/errors; this is required to reset any warnings and er rors that may
occur during operation of the appliance.
You will need:
access to the electrical panel, see Section “Display and knob”.