16
Start up
Switch on the appliance by means of the on/off command (placing it in the "ON"
position).
When activation is successful, the appliance is managed by the S61 controller in its
electrical panel (see Section 3.2 ON-BOARD ELECTRONICS on page 17). The controller’s
display may be viewed through the viewing hole on the front panel of the unit itself.
During operation, the S61 controller displays operating codes.
If the appliance remains inactive for a prolonged period, it is possible that air is present in
the gas pipes. In this case, activation fails and the appliance reports the operating code:
"u_12" - fl ame controller arrest (temporary) (see Section 8.1 MACHINE OPERATING CODES
on page 67) and after a brief interval the appliance automatically launches the start up
procedure again. If code (u_12) is signalled 4 times on successive activation attempts,
the code persists, the appliance locks out the fl ame controller and displays the following
operating code: "E_12" – fl ame controller arrest (see Section 8.1 MACHINE OPERATING
CODES on page 67). In this case reset is not automatic.
To restore operation of the appliance, carry out a reset of the fl ame control unit via menu
2 of the controller: the procedure is illustrated in Section 3.3 RESET OPERATIONS AND
MANUAL DEFROSTINGon page 19. After it is reset, the appliance will make a new attempt
to activate.
If the appliance locks out several times, contact a Potterton Commercial Engineer by
calling the Technical Department of Potterton (tel. 0845 070 1057).
Shut down
Switch off the appliance via the on/off command (placing it in the "OFF" position).
The shutdown cycle takes approximately 7 minutes to complete.
VISUALISING AND RESETTING OPERATING CODES
Operating codes can be generated:
• by the S61 on-board controller;
• by the CCP/DDC (if present).
The operating codes generated by the S61 controller are displayed on its screen and can
also be viewed on the CCI (if present) or DDC (if present).
Operating codes generated by the controller can be cleared through the board itself or
from the CCI/DDC (if fi tted and allowed).
For a description of operating codes generated by the controller and how to clear them,
refer to the list of operating codes contained in Section 8.1 MACHINE OPERATING CODES
on page 67.
The controller (see Figure 5.1 Electronic board S61 on page 37) is located inside the
electrical panel of the appliance and the display may be viewed through the viewing
hole on the front panel of the unit itself.
The Machine Codes generated by the CCI/DDC may only be viewed on the display of the
CCI/DDC and may be cleared only through the CCI/DDC.
For the operating codes generated by the CCP/DDC, refer to the manuals supplied with
the unit.