5-78
PFC-6030 • 5403595 • REV C-1 • 10/13
To configure points:
1. Click on the
Points function
to display the "
Points Configuration" window
.
Figure 103.
Example of a Configuration Window
Note
: Click the columns to sort devices by the field selected, i.e.,
"Name", "Alarm Verification" or "Low Temp Trouble"
.
• Supervisory
– Designates a detector as a supervisory input instead of an alarm input.
• Alarm
Verification
– Specifies that a detector will utilize the alarm verification feature.
• Low Temp Trouble
– Indicates that a device is below 40
̊
F.
2. Devices are listed by “
Built-in SLC”
device addresses, followed by the NACs and I/O circuits.
Note
: Click on the “Device”
field
to sort the list by PWR Supply followed by SLCs.
To configure a single point:
1. Double-click in “
Name
”
field
to enter a descriptive name. The current name is highlighted as shown:
2. Enter a new name (up to 16 alphanumeric characters).
3. Click on drop-down arrow in the
“Function” field
. Select a function type from the list.
Figure 104.
Example of Configuring a “Single” Point
4.
Continue configuring other points, as needed.