5.1 Parameters
5.1.2 Total Groups in the System
For the purpose of group status display and spill zone calculation, the system
needs to know the total number of groups to be installed. The factory default
number is 8.
IMPORTANT: This number must be equal to the total group number used in the
system as planned in Pre-Installation process. If this is wrong, the system may
not work properly.
5.1.1 Console in Group or for AC control
The console sensor can be used for controlling temperature in a group or an
AC unit. In this case, it should be assigned to the AC unit or the group where the
console is installed.
5.1.3 Console Address
Up to two consoles can be installed in one AirTouch 4 system. Each console is set
as Master (1) in default. If two consoles are installed in the same system, one shall
be set to Master (1) and the other is set to Slave (2). The master console will
manage WiFi communications. It’s recommended to set the console in a position
closer to the home router as the master to have a better WiFi communication
between the home router and the AirTouch 4.
NOTE: Each console must have a unique address.
Two consoles with the same address will cause communication problems
between the main control module and the consoles.
NOTE: Touch Save button to save all changes.
Parameters