(657220) Commissioning Notes
1. Wire AirTouch 4, gateway and AC indoor as per diagram below and leave the
dipswitches on the gateway at their default position. Make sure all wires are
connected properly.
2. Initialise the AC Unit with Hitachi AC Wall Controller connected. The Hitachi wall
controller can be wired to A and B terminals in parallel with the gateway.
3. If the Hitachi wall controller is not going to be used after commissioning and
the return air sensor is used for AC temperature control: Turn OFF power and
disconnect the AC Wall Controller from AC Indoor Unit, and set position 1 of
S1 on the gateway to ON (1). Then restart the AC and gateway first and then
power up AirTouch 4. Or power them up at the same time.
4. If AirTouch 4 sensors are used for AC temperature control:
•
Settings on the Hitachi AC wall controller: Set thermostat sensor to the
remote controller (Go to Function Setting, find Item C8, and change its value
to 01). Remove it after the setting if the Hitachi wall controller is not going to
be used after commissioning. Otherwise, set Hitachi AC wall controller as sub
controller (go to Function Setting, find Item code F2, and set its value to 01)
•
Settings on the gateway: set position 1 of S1 on the gateway to ON (1)
•
Settings on the AirTouch 4 screen: Select the required temperature sensor
from the Control Thermistor list in AC setup in the Installer’s settings on
AirTouch 4
•
Restart the AC and gateway first and then power up AirTouch 4. Or power
them up at the same time.
•
Note: Availability of AUTO mode in indoor unit depends on indoor unit
configuration (configuration is made from Hitachi wall controller). If it’s not
configured, changing to Auto will be accepted, but indoor unit will continue in
previous mode.