40
1. Wire AirTouch 4, gateway and AC indoor as per diagram below and leave the
dipswitches on the gateway at their default position. If the indoor unit is a VRF,
please set the correct indoor type as per the Indoor Type Setting table in the
wiring diagram. Make sure all wires are connected properly.
2. Initialise the AC Unit with Toshiba AC Wall Controller connected. The Toshiba
wall controller can be wired to A and B in parallel with the gateway
3. Remove the Toshiba wall controller if it is not to be used after commissioning.
Otherwise, Toshiba’s wall Controller should be always set as Follower
4. If AirTouch 4 sensors are used for AC temperature control, go to AirTouch 4
AC Setup in Installer’s Settings and chose the proper temperature sensor
for AC control.
(657218) Commissioning notes
Wiring Diagrams contd.