D. Installation - Ventilation
D.1.3.6.8 Winter / Summer
Path:
Home
>
Installation>
Climate>
Ventilation>
Conditionings>
Winter / Summer
In case of winter/summer Ventilation, by this setting you can differentiate some parameters in the 2
ventilation systems.
°Temperature differential from summer to winter ventilation: by
this differential (different from normal
Ventilation different.
set in
par. D.1.3.1.F.3)
you can skip multiple system oscillations when
changing from one ventilation system to another.
Summer ventilation air pressure set. In case of winter/summer
ventilation this is the summer ventilation Pressure set and the
winter ventilation
Air pressure set
is the one set par. D.1.2.1.
By setting
Summer press. set= 0
p
this function is excluded.
Transit differential
(Range: 0.0°...
0.5°
...30.0°)
Summer press. set
(Range: 0
P
...
20
P
...300
P
)
D.1.3.6.9 Ventilation delay
Path:
Home
>
Installation>
Climate>
Ventilation>
Conditionings>
Ventilation delay
Start up step, when coming from a stop, to make fan shutters
opening easier (when fans are in speed voltage regulation by
transformer);
this condition remains during the
Shutter start time
.
Time duration of the fan shutters start section.
This is the delay in response when the ambient temperature
requires to switch to a higher step.
On the contrary flaps are operated immediately in order to make
easier flaps opening before the increase in ventilation. In pressure
operation during this delay the flaps will be forced open.
Fan shutters start
(Range: 0...
1
...3)
Shutter start time
(Range:
0
m
.00
s
...10
m
.00
s
)
Vent. increase delay
(Range:
0
m
.00
s
...10
m
.00
s
)