D.1.2.3 Natural
Path:
Home
>
Installation>>
Climate>
Flap>
Natural
D. Installation - Flap
When
Natural Air Flaps
is selected, flaps works according to the signal given by the indoor temperature
probe.
The Temperature Settings of the
Natural Flap
relative set
)
refer
to the set
Ventilation
programmed in
Settings > Climate
(par. C.1
): when changing the main function set (
Ventilation
), the sub-functions
change accordingly.
This Set can be set by Calendar
(par. C.4).
For example with a set
Ventilation=
25.0°
and a
Flap.1 relative set
=
2.0°
the set of temperature working
of the Flap 1 will be of 27.0° (25.0° + 2.0°).
D.1.2.3 Natural> Temperature set
Path:
Home
>
Installation>>
Climate>
Flap>
Natural>
Temperature set
Flap temperature
of the relative probe
Ventilation
Set referred to the
Ventilation
set programmed in
Settings>Climate
This Set can be set by Calendar (see par. C.4).
FLAP
1
When this parameter has a
negative value, it’s deducted
from the Ventilation set.
It’s valid for all relative sets
Flap 2 relative set
C o n t i n u e
until to...
FLAP
2
Flap 1 relative set
Temperature set
of Flap 1 re
ferred to the
Ventilation
set programmed
in
Settings>Climate
(par. C.1).
Temperature set
of Flap 2 re
ferred to the
Ventilation
set programmed
in
Settings>Climate
(par. C.1).
Flap 1 relative set
Flap 2 relative set