D. Installation - Heating
D.1.1.1 Temperature set
Path:
Home
>
Installation>
Climate>
Heating>
Temperature set
These parameters refer to the functioning sets of Heating.
Temperature set of Heating 1 referred to the
Heating
set
programmed
in
Settings>Climate
(par. C.1).
Temperature set of Heating 2 referred to the
Heating
set
programmed
in
Settings>Climate
(par. C.1).
Temperature set of Heating 3 referred to the
Heating
set
programmed in
Settings>Climate
(par. C.1).
Heating temperature differential.
Heating 1
(Range: -30.0°...
0.0°
...30.0°)
Heating 2
(Range: -30.0°...
0.0°
...30.0°)
Heating 3
(Range: -30.0°...
0.0°
...30.0°)
Heating differential
(Range: 0.0°...
0.2°
...30.0°)
Example
-
Heating
=
28.0°
(programmed in
Settings>Climate
par.C.1)
-
Heating 1
(relative set)
= 1.0°
-
Heating differential = 0.2°
As per the above settings the heater starts at 29.0° (
28.0+1.0
) and stops at 29.2° (
28.0+1.0+0.2
).
Same as Heating 2 and Heating 3, but referred to the set
Heating 2
and
Heating 3.
HEAT 1
ON
OFF
Heating
differential
Heating 1 probe
temperature
Set referred to the
Heating
set programmed in
Settings>Climate
(par.C.1)
Heating 1
(relative set)