POK SAS - 18 Cours Antoine Lavoisier - 10400 Nogent-sur-Seine - FRANCE
Phone: +33 (0)3 37 49 53 000 - Email: [email protected] - Web: www.pok-fire.com
MOP_PRO_02341_EN_A - 08/07/2021 - Cop
yright© POK S
A
S - Illustr
ations are only informativ
e
MIXY EDUCTOR
-
Eductor 400 lpm, in aluminium, male inlet and outlet couplings 2" BSP
16
MARK
QTY
DESCRIPTION
CODES
20
1
BODY
15151
21
1
MEMBRANE OF CONTROL VALVE
07220
22
1
CONTROL VALVE BODY
15153
23
1
PROTECTIVE GASKET OF CONTROL VALVE
15182
24
1
SHOULDERED RING
15154
25
1
NUT H M8
-
26
1
FLANGE
15156
27
2
O’RING R27
-
28
2
TBHC SCREW M6X20 STAINLESS STEEL A2 ISO 7380
-
• Dismantling control valve
1 -
Remove the screw (mark 28) and drop off the whole valve
2 -
Unscrew the retainer flange of the control valve body (mark 26).
3 -
With a Allen wrench, unscrew nut (mark 25).
4 -
Drop off the shouldered ring (mark 24) and the calibrated washer (mark 23) and the diaphragm (mark
21).
5 -
Replace the diaphragm by a new one and replace gaskets (mark 27), grease gaskets.
6 -
Reassemble the components in the reverse order and glue screws (loctite 243).
Maintenance
Maintenance