POK SAS - 18 Cours Antoine Lavoisier - 10400 Nogent-sur-Seine - FRANCE
Phone: +33 (0)3 37 49 53 000 - Email: [email protected] - Web: www.pok-fire.com
MIXY EDUCTOR
-
Eductor 400 lpm, in aluminium, male inlet and outlet couplings 2" BSP
11
MOP_PRO_02341_EN_A 08/07/2021 - Cop
yright© POK S
A
S - Illustr
ations are only informativ
e
Technical data
Installation
Instructions for use
Connect the eductor to the water inlet (mark A) and the outlet (mark B) following the directional arrow
engraved on the eductor.
Eductors are settled for indicated flow rate with maximum tolerance of 10% less
and 35% of pressure loss.
There is a direct relationship between the pressure loss and the suction.
Place the eductor between the pump (mark A) and the foam production equipment (mark B).
The suction rod must be emerged in the emulsifier container (mark C).
Please mind the hoses are straight at least within 1 meter at both sides of the eductor when operating.
The eductor must be compatible with the foam producer and take account of the loss of pressure in the
hose.
Pump must be powerful enough to obtain a 150 PSI (10 bar) pressure at the inlet of the eductor.
1 m
1 m
10 bar
150 PSI
6.5 bar
95 PSI
A
B
C
WATER SUPPLY
OUTLET