Pneumax
PTO-Driven Compressor Kit Installation Guide
Page 17 of 36
3. AUTO Mode Adjustment
The pressure for the FIXED mode must have been correctly set before you attempt to adjust
the AUTO mode.
1. Make sure the fire pump is operating at 100 PSI at the main discharge, with minimal
flow.
2. Place the controls on the Auto-Sync control panel to AUTO and RUN.
3. Read the main air pressure and water discharge pressure gauges.
4. The air pressure reading should be equal or up to 5% higher than the water pressure. If
the readings are in this range, go to step 7 and verify the operation at other pressures.
5. If the air pressure is not 5% of the water pressure, adjust it as follows:
•
If the air pressure is too high, turn the Air Inlet Trim Valve clockwise in 1/2 turn
increments to close it, checking air and water pressure after each 1/2 turn.
•
If the air pressure is too low, turn the Air Inlet Trim Valve counterclockwise 1/2 turn to
open it and check pressures. If the air pressure is still too low, open the valve
another 1/2 turn and check the pressures again.
Do not open the Air Inlet Trim Valve more than this. Use the PBTV if the pressure
remains too low.
6. If the air pressure remains too low, close the needle valve on the Piloted Balance Trim
Valve (PBTV) one full turn clockwise and check the pressure gauges.
Repeat closing the PBTV one full turn until the air pressure is equal to or up to 5%
higher than the water pressure.
If the air pressure is too high after a full-turn of the PBTV, turn the Air Inlet Trim Valve
clockwise to lower the pressure until the air pressure is equal to or up to 5% higher than
the water pressure.
7. Verify the Auto-Sync system settings by varying the fire pump discharge pressure and
monitoring the water and air pressure gauges. The air pressure should rise and fall with
the water pressure, matching it within 5%.
Pressures should match at static pressure only. It is normal for the pressures to be
unmatched when flowing water, air, or solution.
Содержание 140-SP
Страница 24: ...PTO Driven Compressor Kit Installation Guide Page 24 of 36 80 SP with 8 inch Vertical Sump Hydraulic Schematic...
Страница 28: ...PTO Driven Compressor Kit Installation Guide Page 28 of 36 Compressor Installation Angles...
Страница 29: ...PTO Driven Compressor Kit Installation Guide Page 29 of 36 Eight Inch Vertical Sump...
Страница 30: ...PTO Driven Compressor Kit Installation Guide Page 30 of 36 Ten Inch Vertical Sump...
Страница 31: ...PTO Driven Compressor Kit Installation Guide Page 31 of 36 80 P Heat Exchanger Oil cooler...
Страница 32: ...PTO Driven Compressor Kit Installation Guide Page 32 of 36 140 200 SP Heat Exchanger Oil Cooler...
Страница 33: ...PTO Driven Compressor Kit Installation Guide Page 33 of 36 80 SP Separator Filter Separator Filter...
Страница 36: ...PTO Driven Compressor Kit Installation Guide Page 36 of 36 Companion Flange Front View Side View...