placing  the  module  on  the  rail,  lift  up  the 
catch. Now, place the module on the rail and 
press  the  catch  to  bring  it  to  the  original 
position.  Make  sure  the  device  is  firmly 
fastened and cannot be easily removed from 
the rail without use of tools.  
For  safety  reasons,  assure  the  safe  distance 
between  live  parts  of  working  module 
terminals and conductive (metallic) elements 
of housing (min. 10 mm) is kept. 
Protect  connecting  wires  from  tearing, 
loosening  and  tensioning  or  built  them  in  in 
such a way that no load is exerted on them. 

 

Space 

requirements 

for 

working 

module 

mounting.

 

 

Methods  of  module  installation:  a)  –  in  modular 
housing  with  access  to  front  surface,  b)  –  in  the 
cover  without  access  to  front  surface,  1-  working 
module, 2 – DIN TS35 rail, 3 – catch. 

12.5

 

 IP protection rate 

Enclosure  of  the  controller’s  executive 
module  provides  various  IP  protection  rates, 
depending  on  the  method  of  installation. 
After  enclosing  in  accordance  with  this 
drawing, the device has protection rate IP20 

from  the  front  side  of  the  executive  module 
enclosure  (specified  on  the  rating  plate). 
From  the  side  of  the  terminals,  the  casing 
has  protection  rate  IP00,  thus  the  terminals 
of the executive module must unconditionally 
be  enclosed,  in  order  to  prevent  access  to 
this part of the casing.  
If it is necessary to access the part with the 
terminals,  disconnect  the  mains  supply, 
make  sure  that  there  is  no  voltage  on 
terminals  and  leads,  and  remove  the 
executive module enclosure. 

12.6

 

 Connecting electrical system 

Controller  is  designed  to  be  fed  with  230 
VAC,  50  Hz  voltage.  The  electrical  system 
should be: 

 

three core, with protective wire PE, 

 

in accordance with applicable regulations, 

 

equipped  with  a    residual  current 
protection  device  (RCD)  with  inrush 
current  IΔn≤30  mA,  protecting  against 
the  effects  of  electric  shock  and  limiting 
damage  to  the  controller,  including 
protection against fire. 

 

After  deactivating  the  controller, 
there  still  can  be  a  dangerous 
voltage  on  the  connections.  Before 
starting  assembly  works  it  is 
obligatory 

to 

disconnect 

the 

electrical  power  and  make  sure 
that  there  is  no  danger  electrical 
power on claps and wires.  

The connection wires should not have contact 
with  surfaces  of  temperature  exceeding  the 
nominal  temperature  of  their  operation. 
Terminals number 1-21 are intended only for 
connecting  devices  with  mains  supply  230 
VAC.  Terminals  22-49  are  intended  for 
cooperation  with  low  voltage  devices  (below 
12 V). 

 

Connecting  mains  supply  230  VAC 
to 

terminals 

22-49 

and 

to 

transmission 

connectors 

will 

damage  the  controller  and  creates 
risk of an electric shock! 

Connect  power  supply  wires  to  terminals 

indicated with an arrow 

 

For  safety  reasons,  the  controller 
must  be  absolutely  connected  to 
the  230  VAC  power  grid,  with  the 
sequence  of  connecting  the  phase 

Содержание ecoMAX860P3-KL

Страница 1: ...EN_DRAFT OLNY APPLIES TO SOFTWARE MODULE A B PANEL v01 XX XX v01 XX XX 09 2019 functions available in the additional module B the ecoSTER TOUCH or ecoSTER200 room panel and ecoNET300 Internet module i...

Страница 2: ...lation etc check if the controller is not connected to the mains Installation should be done by a person with appropriate electrical qualifications Improper cables connection could result in the contr...

Страница 3: ...OUNTING OF MODULE 24 12 5 IP PROTECTION RATE 25 12 6 CONNECTING ELECTRICAL SYSTEM 25 12 7 ELECTRIC SCHEME 27 12 8 CONNECTION OF TEMPERATURE SENSORS 29 12 9 CONNECTION OF WEATHER TEMPERATURE SENSOR 29...

Страница 4: ...er and whether it can cause danger The controller is not an intrinsically safe device which means that in the case of malfunction it can be the source of a spark or high temperature which in the prese...

Страница 5: ...e manual We are not responsible for any damages caused by failure to observe these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentat...

Страница 6: ......

Страница 7: ...USER SETTINGS ecoMAX860P3 KL...

Страница 8: ...l level calibration Burner cleaning Lambda sensor calibration HUW settings Preset HUW temp HUW pump mode Off Priority No priority HUW cont hysteresis HUW disinfection Night time decrease Boiler Off Re...

Страница 9: ...oiler circuit active return protection increasing the preset temperature to load the buffer 5 signaling blowing operation 6 signaling fuel feeder operation 7 signaling CH pump operation 8 signaling HU...

Страница 10: ...the hot user water tank and power heating circuits of mixers 8 5 FIRE UP mode The FIRE UP mode is for automatic firing up of furnace in boiler Total time of firing up proces is dependand on controller...

Страница 11: ...uses power levels defined in Standard mode In this mode the parameters Average hysteresis H2 and MIN hysteresis H1 do not have to be set The Fuzzy Logic mode unlike the Standard mode is not faulty in...

Страница 12: ...ffer decrease of top buffer temperature below preset value Loading start temperature 8 11 GRATE Some boilers have an additional grate to burn other fuels such as wood waste etc To activate the grid mo...

Страница 13: ...automatic detection of summer mode is switched on user can set the parameters Activ temperature SUMMER so outdoor temp above which the summer mode will be switched on and Deactv temperature SUMMER so...

Страница 14: ...e it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recommended to use both these possibilities at the same time Automatic corr...

Страница 15: ...time intervals is indicated by the symbol on the main screen To activate time intervals set the parameter Night time decrease for the given heating circuit to ON The parameter Reduction value set the...

Страница 16: ...y settings will not always correspond to actual fuel consumption so to work correctly this method needs level calibration by controller s user No additional fuel sensors are required Calibration Fill...

Страница 17: ...feeder or other device may cause danger 8 27 Cooperation with room panel The controller can cooperate with room panels All panels has a built in room thermostat This room panels shows useful informati...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX860P3 KL...

Страница 20: ...figure use large nominal diameter pipes and four way valve avoid unnecessary angles and reductions maintain a min 2 horizontal pipe slope etc If the sensor 3 is attached to the pipe isolate it with f...

Страница 21: ...CH and HUW settings Boiler pump YES Service settings CH and HUW settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heatin...

Страница 22: ...gs Loading end temp 75 C Service settings Buffer settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heating curve 0 8 1 4...

Страница 23: ...es connected to the controller During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 12 Controller installation 12 1 Environmental conditions...

Страница 24: ...t exceeded the ventilation holes do not always guarantee that the temperature of the panel surroundings will be lowered in such case use other methods 12 4 Mounting of module Working module has to be...

Страница 25: ...sary to access the part with the terminals disconnect the mains supply make sure that there is no voltage on terminals and leads and remove the executive module enclosure 12 6 Connecting electrical sy...

Страница 26: ...served Controller should be equipped with a set of pins connected to the 230 VAC mains Connect protective wire of power supply cable to ground strip linked with metal boiler housing Connect coupling t...

Страница 27: ...P control panel HW HUW temp sensor type CT4 M1 mixer 1 temp sensor type CT4 WS weather temp sensor type CT6 P RS boiler water return temperature sensor type CT4 FS feeder temp sensor type CT4 OS flam...

Страница 28: ...ower 230 VAC GR grounding strip FU fuse PM2 PM3 mixer pump SM2 SM3 mixer servomotor CPU controlling A main controller connect exclusively with two cables do not connect with four cables as it may lead...

Страница 29: ...contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 12 9 Connection of weather temperature sensor The controller...

Страница 30: ...5 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S 2 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5...

Страница 31: ...elay 12VDC consisting of relay RM 84 2012 35 1012 and base GZT80 RELPOL Standard version of the controller is not equipped with a relay Assembly of relay should be done by a person with proper qualifi...

Страница 32: ...r 2 external alarm annunciator 3 relay 12 17 Connectino of mixer servo During assembly works for mixer servomotor pay attention not to overheat the boiler This may happen when there is a limited flow...

Страница 33: ...properly connected 12 18 Connection of STB temperature limiter In order to prevent the boiler from overheating due to the controller malfunction an STB safety temperature limiter or any other appropr...

Страница 34: ...g time bunrnig off Cleaning airflow Cleaning exh fan Cleaning time Cleaning pause Supervision Supervision time Boiler output Cycle time Blow in output Exh fan output Grate Fuel detection time Flush ti...

Страница 35: ...er temp Max mixer temp Proportional range Integration time constant Valve opening time Pump off by therm Mixer input dead zone Output H OFF Cleaning Alarm Reserve boiler Shunt pump Additional feeder n...

Страница 36: ...to calibrate fuel level The controller process this data if calibration process of fuel level was not done After successful calibration of fuel level the controller does not process this value Feeder...

Страница 37: ...ctivates room thermostat for boiler ecoSTER T1 option available after connecting room panel boiler operation is dependent on room thermostat No1 in ecoSTER ecoSTER T2 option available after connecting...

Страница 38: ...sensor Parameter determines to what maximum temperature HUW container will be heated during cooling the boiler in alarm situations It is a very important parameter because setting too high value of i...

Страница 39: ...he movement of the mixer actuator Increasing this value results in the mixer reaching the set temperature faster Setting this parameter to excessive values causes deregulation of the temperature and u...

Страница 40: ...ing power to the controller Checking the temperature sensor is described in point 12 11 15 4 Feeder temp sensor damage Alarm appears when feeder sensor is damaged or by exceeding measuring scope of th...

Страница 41: ...was before stoppage 16 2 Antifreezing protection When temperature of the boiler decreases below 5 C CH pump will be activated enforcing circulation of boiler water It will delay the process of freezi...

Страница 42: ...umes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sensor readings can be necessa...

Страница 43: ...miter STB is connected to terminals 1 2 then check if the circuit is not cut off due to boiler overheating Check if feeder engine is not broken or damaged In case when engine work can be heard and fue...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www pum pl...

Отзывы: