Can choose between two adjustment modes
responsible for stabilizing the boiler preset
temperature Standard and Fuzzy Logic. This
mode changes in the menu:
Boiler settings
→
Regulation mode
Standard mode operation
If the boiler’s temperature reach preset one
then the controller switches off to the
SUPERVISION mode.
Controller is equipped with boiler’s power
modulation mechanism which allows for
gradual power reduction when approaching
the preset temperature. There are three
power boiler levels: MAX, Average, MIN.
Current power level is displayed on the
screen as 3 segmented indicato rat the left
side of boiler’s icon.
Each level can be allocated with seperate
blow-in output and exhaust output which
influence on actual boiler’s power level.
Power levels parameters are available in the
menu:
Boiler settings
→
Output modulation
The controller regulates burner’s power with
which it operates depending on preset
temperature and defined hysteresis Average
hysteresis H2 and MIN hysteresis H1. It is
possible to configure volumes hysteresis H1
and H2 in such a way that modulation is
done without intermediate position. That
means switching from MAX to MIN with
omission of Aver. power.
Operation in Fuzzy Logic mode
In Fuzzy Logic mode the controller
automatically regulates burner power to
allow boiler operation in such a way to
maintain its temperature on preset level. The
controller uses power levels defined in
Standard mode. In this mode the parameters
Average hysteresis H2 and MIN hysteresis H1
do not have to be set. The Fuzzy Logic mode
unlike the Standard mode is not faulty in
respect of failing to reach the preset boiler
temperature due to incorrect adjustement of
H2 and H1 hysteresis. It also allows for
quicker reach the preset temperature. In
addition, you can adjust the boiler output in
FL mode by the parameters Min boiler output
FL and Max boiler output FL.
Attention: If the boiler operates
without heat buffer and controller is
switched into SUMMER mode than
Standard mode operation of the
controller is recommended.
After exceeding the preset temperature by
5ºC
the
controller
switches
into
SUPERVISION mode.
8.8
SUPERVISION mode
The SUPERVISION mode is applicable either
in regulation in STANDARD and Fuzzy Logic
mode.
The controller switches into SUPERVISION
mode
automatically
without
user’s
intervention:
in Standard regulation mode – after
reaching the boiler preset temperature,
in Fuzzy Logic steering – after exceeding
boiler preset temperature by 5ºC.
In SUPERVISION mode the controller
oversees the furnace, keeping it from
burning off. To do so, the burner operates
with very low power, what together with
properly adjusted parameters do not cause
further increase in temperature. Burner’s
power in SUPERVISION mode and other
parameters of Supervision are grouped in the
menu:
Service settings
→
Burner settings
→
Supervision
Parameters of SUPERVISION mode are to be
set in accordance to burner/boiler producer’s
recommendations. They should be so chosen
Содержание ecoMAX860P3-KL
Страница 6: ......
Страница 7: ...USER SETTINGS ecoMAX860P3 KL...
Страница 18: ...18...
Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX860P3 KL...
Страница 44: ...44...
Страница 45: ...45...
Страница 46: ...46...
Страница 47: ...47...
Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www pum pl...