Can  choose  between  two  adjustment  modes 
responsible  for  stabilizing  the  boiler  preset 
temperature  Standard  and  Fuzzy  Logic.  This 
mode changes in the menu: 
Boiler settings 

 Regulation mode  

 

 

Standard mode operation 

If  the  boiler’s  temperature  reach  preset  one 
then  the  controller  switches  off  to  the 
SUPERVISION mode.  
Controller  is  equipped  with  boiler’s  power 
modulation  mechanism  which  allows  for 
gradual  power  reduction  when  approaching 
the  preset  temperature.  There  are  three 
power  boiler  levels:  MAX,  Average,  MIN. 
Current  power  level  is  displayed  on  the 
screen  as  3  segmented  indicato  rat  the  left 
side of boiler’s icon. 

 

Each  level  can  be  allocated  with  seperate 
blow-in  output  and  exhaust  output  which 
influence  on  actual  boiler’s  power  level. 
Power levels parameters are available in the 
menu: 
Boiler settings 

 Output modulation 

The  controller  regulates  burner’s  power  with 
which  it  operates  depending  on  preset 
temperature  and  defined  hysteresis  Average 
hysteresis  H2
  and  MIN  hysteresis  H1.  It  is 
possible  to  configure  volumes  hysteresis  H1 
and  H2  in  such  a  way  that  modulation  is 
done  without  intermediate  position.  That 
means  switching  from  MAX    to  MIN  with 
omission of Aver. power. 

 

 

Operation in Fuzzy Logic mode 

In  Fuzzy  Logic  mode  the  controller 
automatically  regulates  burner  power  to 
allow  boiler  operation  in  such  a  way  to 
maintain its temperature on preset level. The 
controller  uses  power  levels  defined  in 
Standard mode. In this mode the parameters 
Average hysteresis H2 and MIN hysteresis H1 
do not have to be set. The Fuzzy Logic mode 
unlike  the  Standard  mode  is  not  faulty  in 
respect  of  failing  to  reach  the  preset  boiler 
temperature due to incorrect adjustement of 
H2  and  H1  hysteresis.  It  also  allows  for 
quicker  reach  the  preset  temperature.  In 
addition,  you  can  adjust  the  boiler  output in 
FL mode by the parameters Min boiler output 
FL
 and Max boiler output FL. 

 

Attention:  If  the  boiler  operates 
without  heat  buffer  and  controller  is 
switched  into  SUMMER  mode  than 
Standard  mode  operation  of  the 
controller is recommended. 

After  exceeding  the  preset  temperature  by 
5ºC 

the 

controller 

switches 

into 

SUPERVISION mode. 

8.8

 

SUPERVISION mode 

The  SUPERVISION  mode  is  applicable  either 
in  regulation  in  STANDARD  and  Fuzzy  Logic 
mode. 
The  controller  switches  into  SUPERVISION 
mode 

automatically 

without 

user’s 

intervention: 

 

in  Standard  regulation  mode  –  after 
reaching the boiler preset temperature, 

 

in Fuzzy Logic steering – after exceeding 
boiler preset temperature by 5ºC. 

In  SUPERVISION  mode  the  controller 
oversees  the  furnace,  keeping  it  from 
burning  off.  To  do  so,  the  burner  operates 
with  very  low  power,  what  together  with 
properly  adjusted  parameters  do  not  cause 
further  increase  in  temperature.  Burner’s 
power  in  SUPERVISION  mode    and  other 
parameters of Supervision are grouped in the 
menu: 
Service  settings 

  Burner  settings 

  

Supervision 
Parameters of SUPERVISION mode are to be 
set in accordance to burner/boiler producer’s 
recommendations. They should be so chosen 

Содержание ecoMAX860P3-KL

Страница 1: ...EN_DRAFT OLNY APPLIES TO SOFTWARE MODULE A B PANEL v01 XX XX v01 XX XX 09 2019 functions available in the additional module B the ecoSTER TOUCH or ecoSTER200 room panel and ecoNET300 Internet module i...

Страница 2: ...lation etc check if the controller is not connected to the mains Installation should be done by a person with appropriate electrical qualifications Improper cables connection could result in the contr...

Страница 3: ...OUNTING OF MODULE 24 12 5 IP PROTECTION RATE 25 12 6 CONNECTING ELECTRICAL SYSTEM 25 12 7 ELECTRIC SCHEME 27 12 8 CONNECTION OF TEMPERATURE SENSORS 29 12 9 CONNECTION OF WEATHER TEMPERATURE SENSOR 29...

Страница 4: ...er and whether it can cause danger The controller is not an intrinsically safe device which means that in the case of malfunction it can be the source of a spark or high temperature which in the prese...

Страница 5: ...e manual We are not responsible for any damages caused by failure to observe these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentat...

Страница 6: ......

Страница 7: ...USER SETTINGS ecoMAX860P3 KL...

Страница 8: ...l level calibration Burner cleaning Lambda sensor calibration HUW settings Preset HUW temp HUW pump mode Off Priority No priority HUW cont hysteresis HUW disinfection Night time decrease Boiler Off Re...

Страница 9: ...oiler circuit active return protection increasing the preset temperature to load the buffer 5 signaling blowing operation 6 signaling fuel feeder operation 7 signaling CH pump operation 8 signaling HU...

Страница 10: ...the hot user water tank and power heating circuits of mixers 8 5 FIRE UP mode The FIRE UP mode is for automatic firing up of furnace in boiler Total time of firing up proces is dependand on controller...

Страница 11: ...uses power levels defined in Standard mode In this mode the parameters Average hysteresis H2 and MIN hysteresis H1 do not have to be set The Fuzzy Logic mode unlike the Standard mode is not faulty in...

Страница 12: ...ffer decrease of top buffer temperature below preset value Loading start temperature 8 11 GRATE Some boilers have an additional grate to burn other fuels such as wood waste etc To activate the grid mo...

Страница 13: ...automatic detection of summer mode is switched on user can set the parameters Activ temperature SUMMER so outdoor temp above which the summer mode will be switched on and Deactv temperature SUMMER so...

Страница 14: ...e it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recommended to use both these possibilities at the same time Automatic corr...

Страница 15: ...time intervals is indicated by the symbol on the main screen To activate time intervals set the parameter Night time decrease for the given heating circuit to ON The parameter Reduction value set the...

Страница 16: ...y settings will not always correspond to actual fuel consumption so to work correctly this method needs level calibration by controller s user No additional fuel sensors are required Calibration Fill...

Страница 17: ...feeder or other device may cause danger 8 27 Cooperation with room panel The controller can cooperate with room panels All panels has a built in room thermostat This room panels shows useful informati...

Страница 18: ...18...

Страница 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX860P3 KL...

Страница 20: ...figure use large nominal diameter pipes and four way valve avoid unnecessary angles and reductions maintain a min 2 horizontal pipe slope etc If the sensor 3 is attached to the pipe isolate it with f...

Страница 21: ...CH and HUW settings Boiler pump YES Service settings CH and HUW settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heatin...

Страница 22: ...gs Loading end temp 75 C Service settings Buffer settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heating curve 0 8 1 4...

Страница 23: ...es connected to the controller During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 12 Controller installation 12 1 Environmental conditions...

Страница 24: ...t exceeded the ventilation holes do not always guarantee that the temperature of the panel surroundings will be lowered in such case use other methods 12 4 Mounting of module Working module has to be...

Страница 25: ...sary to access the part with the terminals disconnect the mains supply make sure that there is no voltage on terminals and leads and remove the executive module enclosure 12 6 Connecting electrical sy...

Страница 26: ...served Controller should be equipped with a set of pins connected to the 230 VAC mains Connect protective wire of power supply cable to ground strip linked with metal boiler housing Connect coupling t...

Страница 27: ...P control panel HW HUW temp sensor type CT4 M1 mixer 1 temp sensor type CT4 WS weather temp sensor type CT6 P RS boiler water return temperature sensor type CT4 FS feeder temp sensor type CT4 OS flam...

Страница 28: ...ower 230 VAC GR grounding strip FU fuse PM2 PM3 mixer pump SM2 SM3 mixer servomotor CPU controlling A main controller connect exclusively with two cables do not connect with four cables as it may lead...

Страница 29: ...contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 12 9 Connection of weather temperature sensor The controller...

Страница 30: ...5 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S 2 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5...

Страница 31: ...elay 12VDC consisting of relay RM 84 2012 35 1012 and base GZT80 RELPOL Standard version of the controller is not equipped with a relay Assembly of relay should be done by a person with proper qualifi...

Страница 32: ...r 2 external alarm annunciator 3 relay 12 17 Connectino of mixer servo During assembly works for mixer servomotor pay attention not to overheat the boiler This may happen when there is a limited flow...

Страница 33: ...properly connected 12 18 Connection of STB temperature limiter In order to prevent the boiler from overheating due to the controller malfunction an STB safety temperature limiter or any other appropr...

Страница 34: ...g time bunrnig off Cleaning airflow Cleaning exh fan Cleaning time Cleaning pause Supervision Supervision time Boiler output Cycle time Blow in output Exh fan output Grate Fuel detection time Flush ti...

Страница 35: ...er temp Max mixer temp Proportional range Integration time constant Valve opening time Pump off by therm Mixer input dead zone Output H OFF Cleaning Alarm Reserve boiler Shunt pump Additional feeder n...

Страница 36: ...to calibrate fuel level The controller process this data if calibration process of fuel level was not done After successful calibration of fuel level the controller does not process this value Feeder...

Страница 37: ...ctivates room thermostat for boiler ecoSTER T1 option available after connecting room panel boiler operation is dependent on room thermostat No1 in ecoSTER ecoSTER T2 option available after connecting...

Страница 38: ...sensor Parameter determines to what maximum temperature HUW container will be heated during cooling the boiler in alarm situations It is a very important parameter because setting too high value of i...

Страница 39: ...he movement of the mixer actuator Increasing this value results in the mixer reaching the set temperature faster Setting this parameter to excessive values causes deregulation of the temperature and u...

Страница 40: ...ing power to the controller Checking the temperature sensor is described in point 12 11 15 4 Feeder temp sensor damage Alarm appears when feeder sensor is damaged or by exceeding measuring scope of th...

Страница 41: ...was before stoppage 16 2 Antifreezing protection When temperature of the boiler decreases below 5 C CH pump will be activated enforcing circulation of boiler water It will delay the process of freezi...

Страница 42: ...umes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sensor readings can be necessa...

Страница 43: ...miter STB is connected to terminals 1 2 then check if the circuit is not cut off due to boiler overheating Check if feeder engine is not broken or damaged In case when engine work can be heard and fue...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www pum pl...

Отзывы: