background image

29

TROUBLESHOOTING

PROBLEM 

POSSIBLE CAUSE 

CORRECTIVE ACTION

White powder resi-

due forming within 

burner box or on 

adjacent walls or 

furniture.

1. When heated, the vapors 

from furniture polish, wax, 

carpet cleaners, etc., turn 

into white powder residue.

1. Turn heater off when using furniture 

  polish, wax, carpet cleaner or similar 

products.

Heater produces 

unwanted odors.

1. Heater is burning vapors

  from paint, hair spray, glues, 

etc. See IMPORTANT state-

ment, page 27.

2. Gas leak. See Warning

  Statement, page 27.

3. Low fuel supply.

Heater shuts off 

in use (ODS oper-

ates).

1. Not enough fresh air is

 available.

2. Low line pressure.

3. ODS/pilot is partially

 clogged.

1. Open window and/or door for

 ventilation.

2. Contact local gas supplier.

3. Clean ODS/pilot (see Care and 

  Maintenance, page 25 & 26).

Gas odor exists 

even when control 

knob is in OFF posi-

tion.

1. Gas leak. See Warning

  Statement at top of page 27.

2. Control valve is

 defective.

Moisture/conden-

sation noticed on 

windows.

1. Not enough combustion/

  ventilation air.

Slight smoke or 

odor during initial 

operation

Heater produces 

a whistling noise 

when burner is lit.

1. Residues from

  manufacturing process.

1. Problem will stop after a few hours of 

operation.

1. Turning control knob to high (5) 

position when burner is cold.

2. Air in gas line.

3. Air passageways on

  heater are blocked.

4. Dirty or partially clogged

  burner orifice.

1. Ventilate room. Stop using odor

  causing products while heater is 

 running.

2. Locate and correct all leaks (see 

“Checking Gas Connections,” page 19).

3. Refill supply tank (Propane /LP models).

1. Locate and correct all leaks (see 

  “Checking Gas Connections”, page 19).

2. Contact customer service.

1. Refer to “Air for Combustion and 

  Ventilation” requirements, page 9.

1. Turn control knob to low (1) position and 

let warm up for a minute.

2. Operate burner until air is removed from 

line. Have gas line checked by local 

  propane/LP gas company.

3. Observe minimum installation 

  clearances (Fig. 5,6,7,8 page 13-14).

4. Clean burner (see Care and Maintenance, 

page 25 & 26) or contact customer service.

Содержание VFL-CO18DT

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room i...

Страница 2: ......

Страница 3: ...Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat for propane LP units propane LP gas supply may be low You may feel your gas pressure is too low If...

Страница 4: ...operating this heater safely CALIFORNIA PROPOSITION 65 Fuels used in gas or oil fired appliances and the products of combustion of such fuels contain chemicals known to the state of California to cau...

Страница 5: ...is heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation page 9 If heater keeps shu...

Страница 6: ...5 PRODUCT IDENTIFICATION Grate Cap Grate Piezo Ignitor Battery LP ODS Pilot NG ODS Pilot Grate Locator Spacer...

Страница 7: ...nsed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sal...

Страница 8: ...ft per 1 000 BTU hr 4 8 m 3 per kw of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cu ft per 1 000 BTU hr...

Страница 9: ...TU hr Example Gas heater logs __________BTU hr Gas water heater 30 000 BTU hr Other gas appliances ____BTU hr Vent free heater 26 000 BTU hr Total ____BTU hr Total 56 000 BTU hr Do not include direct...

Страница 10: ...paces see options 1 and 2 Fig 1 You can also remove door into adjoining room see option 3 Fig 1 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation for required siz...

Страница 11: ...appliance is designed for installation in only a solid fuel burning masonry or UL 127 factory built fireplace or in a listed ventless firebox enclosure Exception DO NOT install this appliance in a fac...

Страница 12: ...side of the heater cabinet to any combustible material and wall should follow diagram in Figure 3 B Clearances from the top of the heater opening to the ceiling should not be less than 36 WARNING Mai...

Страница 13: ...thermostat function is prohibited operate manually only Fig 4 Minimum Clearance for Combustible to Wall Fig 5 Heat resistant material slate marble tile etc above fireplace If Using Mantel You must hav...

Страница 14: ...Using a Hood If minimum clearances in Fig 7 1 are not met you must have a hood When using a hood there are still certain minimum mantel clearances required Follow minimum clearances shown in Fig 7 2 w...

Страница 15: ...u may use this heater as a vented product When used as a vented decorative appliance use of the thermostat function is pro hibited operate manually only There are three reasons for operating your heat...

Страница 16: ...Equipment shutoff valve Test gauge connection Sediment trap Tee joint Pipe wrench 3 8 NPT to 3 8 flare fitting UNPACKING 1 Remove logs grate and burner base assembly from carton NOTE Do not pick up bu...

Страница 17: ...degrees and screw it back into the regulator cap by turning it clockwise Replace the cap by turning it clockwise back onto the regulator Make sure the plunger pin and cap are finger tight See Fig 12...

Страница 18: ...cur Install external regulator with the vent pointing down as shown in Fig 15 Pointing the vent down protects it from freezing rain or sleet Purchase the optional equipment shutoff valve from your loc...

Страница 19: ...in the side or bottom of the Mantel Cabinet depending on your particular connection 3 Check all connections for gas leaks NOTICE Most building codes do not permit concealed gas connections Check your...

Страница 20: ...all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff...

Страница 21: ...lace grate burner assembly into firebox with the front pan facing forward Drill two 2 5 32 diameter holes approximately 1 deep Anchor the front pan to the floor using the 2 Concrete Attachment Screws...

Страница 22: ...lied with heater Each log is marked with a number and this number will help you identify each log during installation Provided Logs 6 Fig 19 Installing Log 1 Fig 20 Installing Log 2 Fig 21 Installing...

Страница 23: ...our hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Forced or attempted repair may...

Страница 24: ...ng to light pilot again If after several tries the pilot still goes out turn the gas control knob clockwise to the OFF position and call a qualified service technician 7 Turn control knob counterclock...

Страница 25: ...ave a slight curve but flame should be blue and have no yellow or orange color WARNING If yellow tipping occurs your heater could produce increased levels of carbon monoxide If burner flame pattern sh...

Страница 26: ...free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using...

Страница 27: ...Blow air through the ports slots and holes in the burner 4 Check the orifice holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft clo...

Страница 28: ...itor cable 6 Bad piezo ignitor 7 Bad Battery 1 Replace electrode 2 Replace electrode 3 Replace ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Replace ign...

Страница 29: ...Mainte nance page 25 26 or contact cus tomer service Burner backfiring during combustion 1 Burner orifice is clogged or damaged 2 Burner is damaged 3 Gas regulator is damaged 1 Clean burner orifice se...

Страница 30: ...ective Moisture conden sation noticed on windows 1 Not enough combustion ventilation air Slight smoke or odor during initial operation Heater produces a whistling noise when burner is lit 1 Residues f...

Страница 31: ...1 4 Log 4 1 H 0331 H 331A 1 5 Log 5 1 H 0812 H 0812 1 6 Log 6 1 A 0668 A 0668 2 Grate 1 80 06 041 80 06 042 3 Grate End Cap 1 EXP 4509 EXP 4509 4 ODS Pilot 1 EXP 4046 246 EXP 4046 246 5 ODS Pilot NG...

Страница 32: ...31 33 This limited warranty is extended to the original retail purchaser of this heater and warrants against any 2 2 two two years years...

Страница 33: ...32 34 GHP Group Inc 6440 W Howard St Niles IL 60714 3302 Tel 877 447 4768 www ghpgroupinc com GHP Group Inc 6440 W Howard St Niles IL 60714 3302...

Отзывы: