background image

13

INSTALLATION

MANTEL CLEARANCES

In addition to meeting noncombustible material clearances, you must also meet required clearances 

between fireplace opening and mantel shelf. If the clearances listed below are

not met, you will need a hood.

Determining Mantel Clearances

If you meet minimum clearance requirements between mantel shelf and top of fireplace opening, a 

hood is not necessary (see Fig. 7.1).

  Noncombustible 

  Material Distance 

Requirements for Safe Installation

  8 in. or more 

 

Noncombustible material okay.

  Less than 8 in.   

Noncombustible material must be extended to at least 8 in. See 

   

 

 

 

between 8 in. and 12 in. above. If you can not extend material, you 

   

 

 

 

must operate heater with flue damper open.

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Fig. 7.1 are not met, you must have a hood. When using a hood there 

are still certain minimum mantel clearances required. Follow minimum clearances shown in Fig. 7.2 

when using a hood.

  Fig. 7.1 - Minimum mantel clearances  

 

 

Fig. 7.2 - Minimum mantel clearances  

 

without 

using 

hood 

     when 

using 

hood

NOTICE:

 Surface temperature of adjacent walls and mantels become hot during operation. Walls 

and mantels above the firebox may become too hot to touch. If installed properly, these temperatures 

meet the requirement of the national product standard. Follow all minimum clearances shown in this 

manual.

NOTICE: 

If your installation does not meet the minimum clearances shown, you must do one of

the following: Operate the logs with the flue damper open only. Raise the mantel to an acceptable 

height.

Minimum

20"

Maximum

10"

4" Sheet

Metal Hood

Minimum

10"

Maximum

2.5"

Combustible

 Mantel

Minimum

18"

Maximum

10"

Combustible

Mantel

Содержание VFL-CO18DT

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier This is an unvented gas fired heater It uses air oxygen from the room i...

Страница 2: ......

Страница 3: ...Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat for propane LP units propane LP gas supply may be low You may feel your gas pressure is too low If...

Страница 4: ...operating this heater safely CALIFORNIA PROPOSITION 65 Fuels used in gas or oil fired appliances and the products of combustion of such fuels contain chemicals known to the state of California to cau...

Страница 5: ...is heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation page 9 If heater keeps shu...

Страница 6: ...5 PRODUCT IDENTIFICATION Grate Cap Grate Piezo Ignitor Battery LP ODS Pilot NG ODS Pilot Grate Locator Spacer...

Страница 7: ...nsed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sal...

Страница 8: ...ft per 1 000 BTU hr 4 8 m 3 per kw of the aggregate input rating of all appliances installed in that space and an unconfining space as a space whose volume is not less than 50 cu ft per 1 000 BTU hr...

Страница 9: ...TU hr Example Gas heater logs __________BTU hr Gas water heater 30 000 BTU hr Other gas appliances ____BTU hr Vent free heater 26 000 BTU hr Total ____BTU hr Total 56 000 BTU hr Do not include direct...

Страница 10: ...paces see options 1 and 2 Fig 1 You can also remove door into adjoining room see option 3 Fig 1 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Air for Combustion and Ventilation for required siz...

Страница 11: ...appliance is designed for installation in only a solid fuel burning masonry or UL 127 factory built fireplace or in a listed ventless firebox enclosure Exception DO NOT install this appliance in a fac...

Страница 12: ...side of the heater cabinet to any combustible material and wall should follow diagram in Figure 3 B Clearances from the top of the heater opening to the ceiling should not be less than 36 WARNING Mai...

Страница 13: ...thermostat function is prohibited operate manually only Fig 4 Minimum Clearance for Combustible to Wall Fig 5 Heat resistant material slate marble tile etc above fireplace If Using Mantel You must hav...

Страница 14: ...Using a Hood If minimum clearances in Fig 7 1 are not met you must have a hood When using a hood there are still certain minimum mantel clearances required Follow minimum clearances shown in Fig 7 2 w...

Страница 15: ...u may use this heater as a vented product When used as a vented decorative appliance use of the thermostat function is pro hibited operate manually only There are three reasons for operating your heat...

Страница 16: ...Equipment shutoff valve Test gauge connection Sediment trap Tee joint Pipe wrench 3 8 NPT to 3 8 flare fitting UNPACKING 1 Remove logs grate and burner base assembly from carton NOTE Do not pick up bu...

Страница 17: ...degrees and screw it back into the regulator cap by turning it clockwise Replace the cap by turning it clockwise back onto the regulator Make sure the plunger pin and cap are finger tight See Fig 12...

Страница 18: ...cur Install external regulator with the vent pointing down as shown in Fig 15 Pointing the vent down protects it from freezing rain or sleet Purchase the optional equipment shutoff valve from your loc...

Страница 19: ...in the side or bottom of the Mantel Cabinet depending on your particular connection 3 Check all connections for gas leaks NOTICE Most building codes do not permit concealed gas connections Check your...

Страница 20: ...all leaks immediately 6 Reconnect heater and equipment shutoff valve to gas supply Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff...

Страница 21: ...lace grate burner assembly into firebox with the front pan facing forward Drill two 2 5 32 diameter holes approximately 1 deep Anchor the front pan to the floor using the 2 Concrete Attachment Screws...

Страница 22: ...lied with heater Each log is marked with a number and this number will help you identify each log during installation Provided Logs 6 Fig 19 Installing Log 1 Fig 20 Installing Log 2 Fig 21 Installing...

Страница 23: ...our hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Forced or attempted repair may...

Страница 24: ...ng to light pilot again If after several tries the pilot still goes out turn the gas control knob clockwise to the OFF position and call a qualified service technician 7 Turn control knob counterclock...

Страница 25: ...ave a slight curve but flame should be blue and have no yellow or orange color WARNING If yellow tipping occurs your heater could produce increased levels of carbon monoxide If burner flame pattern sh...

Страница 26: ...free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Your local computer store hardware store or home center may carry compressed air in a can If using...

Страница 27: ...Blow air through the ports slots and holes in the burner 4 Check the orifice holder located at the end of the burner tube again Remove any large particles of dust dirt lint or pet hair with a soft clo...

Страница 28: ...itor cable 6 Bad piezo ignitor 7 Bad Battery 1 Replace electrode 2 Replace electrode 3 Replace ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Replace ign...

Страница 29: ...Mainte nance page 25 26 or contact cus tomer service Burner backfiring during combustion 1 Burner orifice is clogged or damaged 2 Burner is damaged 3 Gas regulator is damaged 1 Clean burner orifice se...

Страница 30: ...ective Moisture conden sation noticed on windows 1 Not enough combustion ventilation air Slight smoke or odor during initial operation Heater produces a whistling noise when burner is lit 1 Residues f...

Страница 31: ...1 4 Log 4 1 H 0331 H 331A 1 5 Log 5 1 H 0812 H 0812 1 6 Log 6 1 A 0668 A 0668 2 Grate 1 80 06 041 80 06 042 3 Grate End Cap 1 EXP 4509 EXP 4509 4 ODS Pilot 1 EXP 4046 246 EXP 4046 246 5 ODS Pilot NG...

Страница 32: ...31 33 This limited warranty is extended to the original retail purchaser of this heater and warrants against any 2 2 two two years years...

Страница 33: ...32 34 GHP Group Inc 6440 W Howard St Niles IL 60714 3302 Tel 877 447 4768 www ghpgroupinc com GHP Group Inc 6440 W Howard St Niles IL 60714 3302...

Отзывы: