Instruction Manual
DM08
One of the following settings can be chosen
("Selection window / make a selection", p. 25):
Setting
Function
not used
no alarm function
>22 mA
rise of current in case of alarm
<3.8 mA
reduction of current in case of
alarm
8.1.9 Simulation
The functional class SIMULATION includes the
functions for simulating output signals or output
states.
If simulation mode is activated, all output sig-
nals will be generated depending on the selec-
ted items. This function enables testing of peri-
pherals connected to the device without water
flow.
Simulation on / off:
The function
Simulation on/off
is intended
for activating or deactivating simulation mode
For selecting the desired function within the
class please use the keys
▲
and
▼
.
After selecting the function
simulation
on/off,
press the ENTER key to display the
current setting:
Simulation
[off]
Example:
For changing the parameter please refer to the
description in Section "Selection window / make
a selection".
Notice
Simulation will be deactivated automat-
ically after restarting the device or
without a keystroke for at least 10 minutes.
Simulation preset value Q / direct:
This function is intended for defining whether a
volume flow rate is preset or the outputs will be
set directly.
For selecting the desired function within the
class please use the keys
▲
and
▼
.
Press ENTER key to display the current selec-
tion for the type of simulation:
Preset of
[direct]
Example:
- 40 -