28 -
STR561 - User manual
Modbus
Address
Description
Read
Write
Reset value
1015
Error flags
Bit 0 = Wrong calibration data
Bit 1 = Wrong parameters
Bit 2 = Wrong status data
Bit 3 = Missing calibration error
Bit 4 = Eeprom writing error
Bit 5 = Eeprom reading error
Bit 6 = Hardware error
Bit 7 = Generic error
Bit 8 = Process error (sensor)
Bit 9 = Parameter out of range
RO 0
1016
Alarms status (0 = None, 1 = Active)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
RO 0
1017
Manual reset: write 0 to reset all alarms.
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
R/W 0
1018
Alarm 1 status (remote control)
R/W 0
1019
Alarm 2 status (remote control)
R/W 0
1020
mA analogue output value (remote control)
R/W 0
1021
Run by serial
0 = Inhibited outputs
1 = Active outputs
R/W 1
1022
Hold by serial
0 = Active analogue input
1 = Analogue input in Hold
R/W 0
1023
Tare zero AI (write 1)
R/W 0
1024
Totalizer reset (write 1)
R/W 0
1025
Peaks reset (write 1)
R/W 0
1026
Sum total (write 1)
R/W 0