User manual - STR561 -
11
+
-
13
7
15
14
1
2
Shield/Schermo
EXC -
EXC +
S + IN
CAL
CAL
S - IN
Strain-gauge
For strain-gauge sensors (4 wires+ 2
calibration wires) or Melt sensors
• Comply with polarity.
• To perform semi-automatic calibration,
connect the 2 calibration wires to the relay
contact Q2 and set properly the parameter
for output Q2.
• When shielded cable is used, it should be
connected to the pin 13 (EXC-).
13
7
15
14
S - IN
S + IN
EXC -
EXC +
Pot
Shield/Schermo
For linear potentiometers
• Use potentiometers with resistive value
greater than 200 Ω.
• When shielded cable is used, it should be
connected to pin 13 (EXC-)
Pixsys code 5300.55.002
5.1.c
Serial input
RS485
16
17
18
Shield/Schermo
RS485 Modbus RTU communication
5.1.d
Relay Q1 output
2A 230V
Resistive
1/8HP
Q1
3
4
Contacts capacity 2 A / 250 Vac for resistive loads.
NB
: see picture below
Содержание STR561
Страница 1: ...STR561 Indicator Indicatore User manual Manuale installatore...
Страница 2: ......
Страница 107: ...Manuale d uso STR561 107 Note Aggiornamenti...
Страница 111: ......