40 - ATR142 -
User manual
21
t.c.
Cycle Time
Cycle time for time-proportioning output (10/15sec for
PID contactors, 1 sec for PID on SSR or value declared by
manufacturer for motorised valves)
0.1-300.0
sec. >
Default
: 10.0.
For motorised valve min. time is 1.0 sec
22
o.po.L.
Output Power Limit
limit of output power %.
10-100
% >
Default
: 100
23
aL. 1
Alarm
operating mode for Alarm 1. Intervention of the alarm is
associated to AL1.
dis.
Disabled >
Default
a. aL.
Absolute Alarm (parameter 12)
b. aL.
Band Alarm (parameter 12)
H.d.aL.
High Deviation Alarm (parameter 12)
L.d.aL.
Low Deviation Alarm (parameter 12)
a.c.aL.
Absolute Command setpoint Alarm
st.aL.
Start Alarm, Active in Run
cooL.
Cooling
t.1.s.a.
Timer 1 Start Alarm
t.1.e.a.
Timer 1 End Alarm
t.1.w.e.
Timer 1 Warning Expiring
t.2.s.a.
Timer 2 Start Alarm
t.2.e.a.
Timer 2 End Alarm
t.2.w.e.
Timer 2 Warning Expiring
t.1.2.s.
Timer 1-2 Start Alarm
t.1.2.e.
Timer 1-2 End Alarm
t.1.2.w.
Timer 1-2 Warning Expiring