AM2020/AFP1010 Troubleshooting Guide 50432 Revision A 8/13/97
42
Corrective Action:
1) Remove power from the AM2020/AFP1010, batteries first and then AC. Wait
one minute. Reapply power - AC first, then batteries.
2) If the trouble does not clear, call Notifier Technical Support.
This is an indication that the 20-conductor ribbon cable (part number 71046) that
connects the DIB (Plug J4) to the SIB (Plug P4) is either missing or defective.
Corrective Action:
1) Verify that the cable is in place and is plugged in correctly.
2) Remove the cable and check the continuity with a voltmeter.
3) If the trouble does not clear, call Notifier Technical Support.
A NFN communications fault has been detected on the indicated port. This
trouble may be due to disconnected or faulty media.
Corrective Action:
1) Verify wire/fiber is connected.
2) Use the MET-1 to evaluate the wire.
3) Verify NFN configuration (MIB thresholds, node address and port configura
tion).
4) Cycle power.
5) If the trouble does not clear, call Notifier Technical Support.
A NFN communications fault has been detected on the indicated port. This
trouble may be due to disconnected or faulty media.
Corrective Action:
1) Verify wire/fiber is connected.
2) Use the MET-1 to evaluate the wire.
3) Verify NFN configuration (MIB thresholds, node address and port configura
tion).
4) Cycle power.
5) If the trouble does not clear, call Notifier Technical Support.
The Upload/Download must be enabled in Partial System Programming. A TF6
Trouble Code will be produced if the EIA-485 Interface is not communicating at
all with the peripheral device.
Corrective Action:
1) Make sure that the Upload/Download has been enabled in programming.
2) Verify that the wiring between the 485 Interface and the computer is correct.
TF3 DIB to SIB Cable
Bad or Missing.
TF4 Communication Link
Failure in Port A.
TF5 Communication Link
Failure in Port B.
TF6 Upload/Download
Communications Fault.
www.PDF-Zoo.com
firealarmresources.com
Содержание Notifier AFP1010
Страница 45: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 45 NOTES www PDF Zoo com firealarmresources com...
Страница 46: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 46 NOTES www PDF Zoo com firealarmresources com...
Страница 47: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 47 NOTES www PDF Zoo com firealarmresources com...