AM2020/AFP1010 Troubleshooting Guide 50432 Revision A 8/13/97
16
The MPS-24A and MPS-24B Main Power Supplies are designed to withstand
IEEE 587 Category A Long Branch Circuits transients. They have been tested to
this standard by Underwriter's Laboratories as part of the UL 864 tests. The
power supplies use Metal Oxide Varistors (MOVs) to achieve this degree of
protection.
The LIB-200 Loop Interface Board is designed to exceed
FCC Part 68 Subpart D
Telecommunication Line Transient standards. Underwriter's Laboratories has
tested the LIB-200 to the UL 864 signal line transient level. The LIB-200/200A/
400 uses gas discharge tubes and zener diodes for this protection.
The MPS-TR is designed to supervise any of the MPS series power supplies
when they are remotely mounted.
Yes. Presently, there is only one way to reset the AM2020/AFP1010 from a
keyswitch (either remotely or locally). Take a normally open keyswitch (that when
rotated momentarily closes) and connect it to a control input point on an LDM-32
Lamp Driver Module. This annunciator point must be programmed with a
"ARES" (Annunciator Reset) type ID. Whenever the keyswitch is activated, the
Fire Alarm Control Panel will be reset.
Note: If this keyswitch is mounted remotely from the FACP, Underwriter's Laboratories
requires that the status of all fire alarm zones be annunciated at this remote location.
What Type of Transient
Protection does the
AM2020/AFP1010 Have?
What is the MPS-TR
Used For?
Can I Reset the AM2020/
AFP1010 From a
Keyswitch?
www.PDF-Zoo.com
firealarmresources.com
Содержание Notifier AFP1010
Страница 45: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 45 NOTES www PDF Zoo com firealarmresources com...
Страница 46: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 46 NOTES www PDF Zoo com firealarmresources com...
Страница 47: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 47 NOTES www PDF Zoo com firealarmresources com...