AM2020/AFP1010 Troubleshooting Guide  50432  Revision A  8/13/97

13

If the symptoms at the left exist, it could be an indication of a power supply
problem.

Corrective Action:

1) On the MPS-24A Main Power Supply, with the main power harness that

connects the MPS-24A to the ICA-4L (part number 71030) plugged in,
measure with a voltmeter either Plug P2 or P4, pin 1 (-) to pin 8 (+).

Figure 2-11: The Upper-Right Corner of the MPS-24A

2) The voltage reading should be 5.0 VDC.  If this voltage reading is below 4.7 or

above 5.25 VDC, replace the MPS-24A.

3) Record the software EPROM numbers from the CPU, each LIB, SIB, and DIA

and contact the Notifier Technical Service Representative for further instruc-
tion.

This is caused by a short circuit in the wiring of either a Control Module or an
XPC point.

Corrective Action:

1) Check field wiring.

2) Check the style of the field wiring (Style Y or Z).

3) Remove field wiring and place ELR on screw terminals.

4) Check Type I. D.

5) Replace module or XPC card.

This is caused by an open circuit on the NAC  of either a Control Module or an

XPC point.

Corrective Action:

1) Check field wiring.

2) Check the style of the field wiring (Style D or B).

3) Remove field wiring and place ELR on screw terminals.

4) Replace module or XPC card.

Original MPS-24A

24 VDC (Pin 7)

5 VDC (Pin 8)

Common (Pins 1-4)

Revised MPS-24A

24 VDC (Pin 7)

5 VDC (Pin 8)

Common (Pins 1-4)

Display Trouble LED is
Constantly Illuminated,
Piezo Sounder is Soun
ing Steadily and the AC
Power LED is Flashing
Slowly.

Short Circuit From a
Control Module or XPC
Point.

Open Circuit From a
Control Module or XPC
Point.

www.PDF-Zoo.com

firealarmresources.com

Содержание Notifier AFP1010

Страница 1: ...AFP1010 Troubleshooting Guide DOCUMENT NUMBER 50432 8 13 97 REVISION A 50432 A ECN 97 333 12 Clintonville Road Northford CT 06472 Phone 203 484 7161 Fax 203 484 7118 www PDF Zoo com firealarmresource...

Страница 2: ...oper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instru...

Страница 3: ...ystem Will Not Accept Any New Programming Information 17 The System Loses all Programmed Information 17 The Operator Gets Kicked out of Programming Every Time a New Point is Added 18 The Piezo Sounder...

Страница 4: ...power from the panel 4 Allow the panel to discharge for approximately one minute before connect ing or disconnecting any ribbon cables or harnesses or removing or adding any circuit boards When reapp...

Страница 5: ...this circuit is shown below Point a on the schematic represents the electrical location of the cabinet which is at earth ground potential During a normal condition the pulse detection circuitry detec...

Страница 6: ...It is important to realize that these paths to ground need not be dead shorts In the very common case shown below multiple seemingly minor ground faults combine to exceed the ground fault threshold of...

Страница 7: ...will fall below the ground fault circuit threshold and a ground fault indication will result When using shielded cable for the SLC loop wiring it is important to realize that since a conductor the SL...

Страница 8: ...it goes below 50 000 ohms a ground fault will result That means that 12 73 microfarads is the maximum allowable amount of capacitance collectively on all loops leaving the panel Figure 2 7 Schematic r...

Страница 9: ...t condition 5 Disconnect all field wiring from terminal block TB3 on the MPS 24A 6 Power down the panel Disconnect the ribbon cable that connects the SIB plug P4 to the DIA plug P4 Disconnect the ribb...

Страница 10: ...tion replace the faulty ICA 4 ICA 4L chassis and return the LIBs to their original positions For more information on LIB corrective action refer to Section Five Trouble Code T18 Drift Compensation Err...

Страница 11: ...munications Invalid Reply clears Corrective Action If power has not been removed from the system recently and a Drift Compen sation error is present follow the procedure below 1 Remove the detector in...

Страница 12: ...tripped 4 Reapply power to the system and measure pin 1 and pin 7 of P2 or P4 again with the harnesses disconnected If 24 VDC is not present the main power supply must be replaced If 24 VDC is presen...

Страница 13: ...a short circuit in the wiring of either a Control Module or an XPC point Corrective Action 1 Check field wiring 2 Check the style of the field wiring Style Y or Z 3 Remove field wiring and place ELR...

Страница 14: ...10L is an older pull station which is no longer available it should be programmed as a PULL The BGX 101L the most common pull station must be programmed as an MPUL 4 Once the programming has been veri...

Страница 15: ...e pro grammed with an FORC CMXC or other similar type I D 4 Confirm that each address point on each of the expander cards is pro grammed appropriately If performing Canadian Dual Stage with XPC cards...

Страница 16: ...on The MPS TR is designed to supervise any of the MPS series power supplies when they are remotely mounted Yes Presently there is only one way to reset the AM2020 AFP1010 from a keyswitch either remot...

Страница 17: ...ould come from remotely powered annunciators If an annunciator is powered from a remote source this source of power may back feed into the control panel through the EIA 485 connection on the Serial In...

Страница 18: ...ll Point Programming 4 Do not acknowledge this trouble 5 Instead immediately reenter Full Point Programming and begin to program the next point As soon as the user reenters Full Point Programming the...

Страница 19: ...er number FZON In addition once activated an FZON will execute it s Control By Event CBE list which can only consist of a number of things to activate Example Let s assume that Zone 10 and Zone 11 are...

Страница 20: ...above examples a reverse activated zone Zone 208 may reference another RZON Zone 201 in it s equations provided that the zone that it is referencing is numerically lower The OR function may reference...

Страница 21: ...ivalent of a three input AND equation The above equation can also be visualized in electrical terms as three normally open switches in series Figure 3 7 Electrical equivalent of a three input AND equa...

Страница 22: ...NE Zn Example 1 Assume that Zone 220 is a reverse activated zone with the following Control By Event equation XZONE Z48 This means that when any two or more initiating devices detectors monitor module...

Страница 23: ...ilding are mapped to Zone 1 an FZON All the pull stations in the building are mapped to Zone 200 an RZON The control modules that control the main sounders in the building are also mapped to Zone 200...

Страница 24: ...at Zone 236 will be activated everyday of the week excluding Saturdays and Sundays from 8 00 AM until 5 00 PM Example of Equation Type 2 Assume that Zone 225 is a reverse activated zone with the follo...

Страница 25: ...ped to Zone 200 Zone 200 is given the following CBE SDEL 00 01 00 Z1 When a smoke detector goes into alarm it activates Zone 1 A counter is started that will delay the activation of Zone 200 for one m...

Страница 26: ...Sensitivity in either Full or Partial System Program ming 2 Assign Zone 240 reverse activated as the High Day Night zone 3 Set the sensitivity of all the addressable detectors to MEDIUM in Full or Pa...

Страница 27: ...alarm points to latching operation Selected Listing NFPA Standard Default Module Programming 72A NFPA 72 1993 Local Fire Alarm Systems L1M96 EVGA Type ID Must be used to activate Notification Applianc...

Страница 28: ...ng the CRT to the panel and connecting it to the SIB with a short length of cable If it still does not function replace the CRT The AM2020 AFP1010 is not receiving the proper handshaking signal from t...

Страница 29: ...s not correct noise problems Further troubleshooting is recommended check wiring and or call Notifier Technical Services for more information No In Full or Partial Point Programming the control panel...

Страница 30: ...allel We recommend that during program ming the LCD 80 should be disconnected to avoid unwanted interference from terminal supervision messages sent from the LCD 80 to the fire alarm control panel How...

Страница 31: ...20 AFP1010 batteries first and then AC Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support During the normal CPU polling response cycle which is expla...

Страница 32: ...power from the AM2020 AFP1010 batteries first and then AC Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support SCB stands for Serial Communication Bus...

Страница 33: ...is specific trouble will be generated if the AVPS 24 is not programmed into the system and the trouble cable is connected to the CPU Corrective Action 1 Program the AVPS 24 into the system using eithe...

Страница 34: ...Section 2 AM2020 AFP1010 Hard ware This trouble will occur if the standby batteries have been disconnected This trouble will also be generated if the batteries have become severely over or under charg...

Страница 35: ...nstalled in the ICA 4L chassis but has not been programmed in Full or Partial System Programming Second if the LIB has been programmed but has not been physically installed This trouble will also occu...

Страница 36: ...ation that one of the SLC loop drivers on the LIB board has failed Corrective Action 1 Confirm that the loop wiring matches the LIB programming 2 Remove the field wiring from the LIB in case there is...

Страница 37: ...then AC Wait one minute Reapply power AC first then batteries 2 If the trouble does not clear call Notifier Technical Support Trouble Codes T2C T3C T4C etc apply to Loop Interface Boards 1 through 10...

Страница 38: ...ming 5 Replace the CRT Corrective Action for LCD 80 inTerminal Mode 1 Check 485 wiring 2 Check that SW3 1 and 2 are set properly for all LCD 80s that exist 3 If you have both LCD 80 and CRT is the CCM...

Страница 39: ...tifier Technical Support Each time the system is powered up or reset the DIB performs a test of the operating system EPROM on the DIB board by looking at the checksum This trouble is generated if the...

Страница 40: ...n error condition on the printer Corrective Action 1 Verify that the printer is on line 2 Verify that the printer has paper and it is not jammed 3 Make sure the EIA 232 is plugged into the correct por...

Страница 41: ...ed if the CPU has tried to send the same message to the ISIB several times and each time the message was received it was invalid Corrective Action 1 Remove power from the AM2020 AFP1010 batteries firs...

Страница 42: ...nfiguration MIB thresholds node address and port configura tion 4 Cycle power 5 If the trouble does not clear call Notifier Technical Support A NFN communications fault has been detected on the indica...

Страница 43: ...FN configuration MIB thresholds node address and port configura tion 4 Cycle power 5 If the trouble does not clear call Notifier Technical Support An undefined trouble has occurred in the system Corre...

Страница 44: ...rophone on the AMG for 20 seconds 2 Check if the AMG microphone is unplugged 3 Check if the FFT 7 wiring is correct 4 Check if the SCS has correct programming of its switch groups 5 Check if the UDACT...

Страница 45: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 45 NOTES www PDF Zoo com firealarmresources com...

Страница 46: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 46 NOTES www PDF Zoo com firealarmresources com...

Страница 47: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 47 NOTES www PDF Zoo com firealarmresources com...

Страница 48: ...s NO NO NO NO NOTIFIER TIFIER TIFIER TIFIER TIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for whi...

Отзывы: