AM2020/AFP1010 Troubleshooting Guide 50432 Revision A 8/13/97
27
Example: If the user selects NFPA 72B listing, the panel will automatically program in a
control module at address L1M97 and assign it a type ID of "GAS" (general alarm -
supervised). As per NFPA 72-1993 Auxiliary Fire Alarm Systems (formerly NFPA 72B),
this control module must be used to trip a local energy type municipal box.
Note: A control module must physically be installed on the SLC loop and set to this
address otherwise an "invalid reply" will occur.
Note: Selection of NFPA 72A listing automatically defaults all fire-alarm points to "latching"
operation.
Selected Listing
NFPA Standard
Default Module Programming
72A
NFPA 72-1993
Local Fire Alarm Systems
L1M96 - "EVGA" Type ID
Must be used to activate Notification Appliances
during a general alarm condition.
72B
NFPA 72-1993
Auxiliary Fire Alarm Systems
L1M97 - "GAS" Type ID
Must be used to connect to a Municipal Box for the
purpose of alarm transmission.
72C
NFPA 72-1993
Remote Station Fire Alarm Systems
L1M98 - "GAC" Type ID
L1M99 - "GAC" Type ID
Must be used to connect to a polarity reversal
circuit of a remote station for the purpose of alarm
transmission.
72D
NFPA 72-1993
Proprietary Fire Alarm Systems
None
71
NFPA 72-1993
Central Station Fire Alarm Systems
None
RCV
Receiving Unit and Central Station Unit
None
www.PDF-Zoo.com
firealarmresources.com
Содержание Notifier AFP1010
Страница 45: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 45 NOTES www PDF Zoo com firealarmresources com...
Страница 46: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 46 NOTES www PDF Zoo com firealarmresources com...
Страница 47: ...AM2020 AFP1010 Troubleshooting Guide 50432 Revision A 8 13 97 47 NOTES www PDF Zoo com firealarmresources com...