Pittway ID1002/16 Скачать руководство пользователя страница 38

997-340-001, Issue 8
April 1998

ID1000 Series Operating Manual

FAULT CODES - POSSIBLE CAUSES & REMEDIES

1

Loop card missing or failed to respond. Possible causes are:

- Wrong ribbon cable connected

- Ribbon cable disconnected

- Loop card failure.

For last case, change the loop card.

5

Loop card CPU power restart. Possible cause:

- Loop card failure

Change the loop card.

9

A short circuit has occurred on loop X. If isolators are fitted, the system shows NO
REPLY/MISSING for the devices located between the isolation points.

Disconnect the affected section of the loop and use a meter to find the fault.

13

This indicates that a device has been installed without setting a valid address, i.e. left at
factory default of ‘00’.

17, 21

Either fault code indicates a loop card failure.

Replace the loop card.

25

Data returned from a loop device is being corrupted over a period of time. Check:

- The continuity of loop screens

- The screen is connected to earth at one point only (normally at the panel)

- Ferrite suppressors are fitted to loop wiring at the control panel.

32

This fault indicates that the peripheral unit has not responded to the enquiry code sent or
the link to the third party equipment is not connected (this would normally indicate a fault
in the external device).

First check by replacing the unit with an RS232 monitor or device that is known to work.
If this checks out OK, replace unit. If not, change the CPU PCB.

33

This indicates that the incoming supply has failed. Check the following:

- Blown mains fuse (FS1)

- Failed 240VAC mains supply failure

- Failed PSU transformer

34

This fault indicates the occurence of one or more of the following:

- Battery charger fuse (FS5) has blown

- Faulty PSU PCB

- Faulty batteries

Replace items as required.

35

Check fuse FS6 on the PSU PCB. If OK, check the 24V regulator or PSU PCB.

Replace as necessary.

36

This fault code indicates one of the following conditions has occurred:

- No continuity exists between the 24V AUX output and 24V monitored input

- 27V AUX supply fuse (FS2) has blown

- Faulty PSU PCB.

37, 38, 39

Should any of these faults occur change the Display/RS485 PCB assembly (PN 124-153).

34

Содержание ID1002/16

Страница 1: ...ATING MANUAL Ref 997 340 001 Issue 8 April 1998 NOTIFIERLimited CharlesAvenue BurgessHill WestSussex RH15 9UF Tel 01444 230300 Fax 01444 230888 Note This manual applies only to panels with software ve...

Страница 2: ...ammable materials overloaded electrical circuits children playing with matches or arson Audible warning devices such as bells may not alert people if these devices are located on the other side of clo...

Страница 3: ...ntrol Output Test CMX Modules 8 3 9 2 2 Control Output Test Local Sounder Circuits 9 3 9 3 Sensor Automatic Test 10 3 9 4 Replace sensor 10 3 10 Setting the Clock 11 3 11 Display and or Log Device Dat...

Страница 4: ...Status 28 6 1 10 Panel PRINTER Control Status 28 7 MENU MAPS 29 Figure 7 1 Top Level Menu Options 29 Figure 7 2 TEST Menu Options 30 Figure 7 3 SET CLOCK Menu Option 30 Figure 7 4 MASK UNMASK Menu Opt...

Страница 5: ...using the pushbuttons on the front of the panel alone many of them can on some installations also be carried out by use of function keys on a remote VDU terminal or by operation of remote switches con...

Страница 6: ...emises is achieved or at the direction of an authorised person the Alarm sounders may be silenced by pressing the SILENCE SOUNDERS pushbutton If there are any delayed operations for which the timer ha...

Страница 7: ...as SYSTEM FAULT xx where xx is a number of up to 2 digits e Operation of the fault transfer relay for automatic alert to a service centre 2 6 FAULT Recommended Operator Actions a Press MUTE INTERNAL S...

Страница 8: ...ogramming Manual for more details 997 340 000 and 997 340 003 Pressing any disabled function key will cause an internal beep and a refresh of the display 3 2 Top Level Display Except when some operato...

Страница 9: ...recorded as missing Press ENTER at any time when the display is scrolling and the system if appropriate displays Log each missing device individually Y N If YES is pressed all the individual devices i...

Страница 10: ...Press this pushbutton or the appropriately labelled VDU key or remote switch if available to reset the system completely except after an EVACUATE operation Provided that no FIRE PRE ALARM or FAULT co...

Страница 11: ...walk round test of sensors or MCPs select 0 and see Section 3 9 1 To carry out a Control Output test select 1 and see Section 3 9 2 To perform the daily or weekly sensor automatic test select 2 and se...

Страница 12: ...e test condition is removed In the case of a Manual Call Point test the appropriate sounder outputs are activated according to the specified test requirements either for approximately one second or fo...

Страница 13: ...ENTER details of the existing module nearest in number to what you typed are shown and you may then continue to step up or down from that point Press ENTER a second time to finally select the module N...

Страница 14: ...but with the message Weekly automatic test in progress or Daily automatic test in progress on line 2 of the display this message also appears when the test is in progress at the scheduled time for as...

Страница 15: ...ate on which it had been operating or at the time when the clock was last reset whichever was the later Press Pushbutton 3 The clock display will be frozen and the display will show SETTING CLOCK date...

Страница 16: ...Dump The option required is 0 The display then shows 0 Sensors 1 Modules Press the appropriate pushbutton depending on whether you want to inspect Analogue sensors or Monitor Control modules If after...

Страница 17: ...andard display press CANCEL on VDU press ctrl X Alternatively you may continue to use the up and down arrows to examine other devices data The LED pulsing option is only available from the panel keypa...

Страница 18: ...Confirm Y N to which YES should be answered to complete the set up NO to cancel the whole procedure The maximum store capacity depends on the available memory and if another sensor is already being l...

Страница 19: ...rinted This is the only occasion on which a list of devices at another panel can be obtained Note that only one of the above special options at a time can be selected i e you cannot print out selectiv...

Страница 20: ...flash Use the and arrows in the same way to step back and forward an hour at a time times will be rounded to the nearest hour When you press ENTER again the first event which occurred after the selec...

Страница 21: ...ed after a set time out or at certain times of the day Time of day controlled MASK and UNMASK are possible with software versions 3 32 and 1 32 using two new Control Matrix types TRUE and FALSE Note T...

Страница 22: ...l then displays one of the following depending on your selection UNMASK ALL devices zone n Y N or MASK SENSORS in zone n Y N or MASK ALL inputs zone n Y N or MASK ALL devices zone n Y N If you choose...

Страница 23: ...that it refers to the Slave panel Then the system displays 0 Unmask 1 Mask Press 0 or 1 as required Unlike when masking local zones there is no option to specify whether sensors all inputs or input a...

Страница 24: ...requests you to choose between temporary and permanent mode as described in Section 3 14 1 See that section for further details 3 14 3 Mask and Unmask Complete Zone via Remote Switch This function is...

Страница 25: ...ation 4 1 MUTE Internal Sounder Press Function Key F10 The same MUTE operations as defined in Section 3 3 are carried out but there is no scrolling display and no review of other events outstanding 4...

Страница 26: ...puts without the need for access to the panel Operate the switch as indicated so as cause the sounders or other outputs to operate in the pre programmed pattern Release the switch so as to switch off...

Страница 27: ...ditions 6 1 1 Panel NORMAL Status This is the condition of the panel when it is operational and there are no uncleared FIREs or FAULTs no part of the system is MASKED and no TESTing or CONFIGURATION i...

Страница 28: ...me of alarm location date time of alarm plus indication as to whether any further alarms exist indicated by MORE PRESS or Internal sounders if not accepted Fire sounder high pitched on STEADY if accep...

Страница 29: ...ed by MORE PRESS or Internal sounders Fire sounder high pitched on intermittently one bleep every 2 minutes Circuits Controlled Internally and External Devices Programmed function 6 1 4 Panel FAULT St...

Страница 30: ...on all other sensors and modules should either give short pulses or be OFF altogether 6 1 5 Panel DEVICES MASKED Status This is indicated when some or all of the sensors or modules of the system have...

Страница 31: ...dules those for which the control output is ON also be on STEADY The LEDs of all other sensors and modules should either give short pulses or be OFF altogether 6 1 7 Panel TEST Status This is the cond...

Страница 32: ...y identical to the NORMAL status except that a special option has been selected by the authorised engineer to partially inhibit the functioning of the fault buzzer Operation of the FIRE internal sound...

Страница 33: ...ted in Figures 7 1 to 7 5 Refer to the ID1000 Series Programming Manual 997 340 003 for the menu map on programming functions accessed through pressing 4 on the numeric keypad Note Tinted boxes are us...

Страница 34: ...997 340 001 Issue 8 April 1998 ID1000 Series Operating Manual Figure 7 2 TEST Menu Options Figure 7 3 SET CLOCK Menu Option 30...

Страница 35: ...997 340 001 Issue 8 April 1998 ID1000 Series Operating Manual Figure 7 4 MASK UNMASK Menu Options Figure 7 5 LOG DISPLAY Menu Options 31...

Страница 36: ...ey are supervising Possible types are for input MMX types MCP Manual call point MON General monitoring function SPRK Sprinkler switch monitoring AUX Auxiliary non latching input For output CMX types C...

Страница 37: ...olts supply failed or voltage outside limits 36 Auxiliary 24 volts supply failed or voltage outside limits 37 Fire Transfer relay monitored fault 38 Fault Transfer relay monitored fault 39 Evacuate Tr...

Страница 38: ...ally at the panel Ferrite suppressors are fitted to loop wiring at the control panel 32 This fault indicates that the peripheral unit has not responded to the enquiry code sent or the link to the thir...

Страница 39: ...ult occurs change the PSU PCB 50 This fault code indicates a short circuit fault on sounder circuit 2 wiring Disconnect the wiring and use a meter to locate the fault 51 This fault code indicates a sh...

Отзывы: