997-340-001, Issue 8
April 1998
ID1000 Series Operating Manual
APPENDIX 1
AVAILABLE LOOP DEVICE TYPES
There are six types of analogue sensors:
VIEW (Laser-based Smoke):
Type LPX-751
OMNI (Combined Heat/smoke):
Type IPX-751
IONISATION SMOKE:
Type CPX-551/CPX-751
OPTICAL (PHOTOELECTRONIC) SMOKE:
Type SDX-551/SDX-751
HEAT (THERMAL) Grade 2
Type FDX-551
HEAT (THERMAL) Grade 1
Type FDX-551R
and ten types of module:
Manual Call Point (MCP)
Type M500KACGB
ZONE INTERFACE
Type ZMX-1
LASER BASED ASPIRATING DETECTOR & INTERFACE
LaserStar
MONITOR:(input only)
Type MMX-1
MINI-MONITOR:(input only)
Type MMX-101
MICRO-MONITOR:(input only)
Type M503ME
CONTROL:(input/output)
Type CMX-2
10-WAY MONITOR CARD
Type MMX-10
10-WAY CONTROL RELAY CARD
Type CMX-10R
Loop-powered Sounder
Type AB**, AN**
Note: The ZMX-1 is a lower cost alternative to the Conventional Detector Interface (CDI). However,
the two devices are not interchangeable unless a configuration change is made in the panel.
These modules may be further designated according to the type of equipment which they are
supervising. Possible types are, for input (MMX types):
MCP
Manual call point
MON
General monitoring function
SPRK
Sprinkler switch monitoring
AUX
Auxiliary non-latching input
For output (CMX types):
CTRL
General control output
BELL
Bell, loop-powered sounder or other sounder
CDI
Conventional Detector Interface.
Note 1: In ID1000 Series systems fitted with earlier versions of software, up to 2.14, 1.12, 3.12, the
type CONV was also possible with MMX modules. This facility is incompatible with
NOTIFIER Limited’s Conventional Detector Interface (CDI) and has now been withdrawn.
Note 2: For newer versions of software (i.e. 3.30 and 1.30, or later) the new device type CONV is
now re-named as device type CDI; this is to distinguish it from the new device type ZMX.
Note 3: Device type HAL has been withdrawn.
Isolators
In addition there is a non-addressable isolator module (type ISO-X) which has the capability to isolate
sections of the loop in the event of short-circuit.
Relays
The panel also has four general purpose relays for the purpose of switching auxiliary equipment,
three of which are designated FIRE, FAULT and EVACUATE transfer, the fourth being SPARE and
programmable, plus two 1-amp programmable, monitored sounder circuits.
32