997-340-001, Issue 8
April 1998
ID1000 Series Operating Manual
Press YES to perform the test. In order to switch off the sounder quickly, simply press SILENCE
SOUNDERS. However, if you do not want silence sounders elsewhere, to remain on because of an
Alarm or Evacuate condition, you will have to repeat the sequence above.
3.9.3
Sensor Automatic Test
This option is only available if the panel is already configured so as to perform this test daily or weekly
at a programmed time of day. This test differs from the normal walk test in that no part of the panel is
taken off watch for more than a few seconds, and no operator intervention is normally required unless
a fault is detected. There is normally no need to force the panel to undergo this test ahead of the
scheduled time, but if you need to do so, press key ‘0’, as detailed in Section 3.9, followed by ‘2’ to
select the option Weekly or Daily Automatic Test (the prompt indicates at what interval the automatic
test is normally scheduled). The panel now displays:
Confirm (Y/N)?
Answer YES to start the test. The panel will revert to the normal top-level display, but with the message:
Weekly automatic test in progress
or
Daily automatic test in progress
on line 2 of the display (this message also appears when the test is in progress at the scheduled time)
for as long as the test is under way (the length of time depends on the configuration of the panel, but
will typically be 10-15 minutes).
Note: If you initiate a zone walk test (as described in Section 3.9.1), or if a FIRE is detected elsewhere
in the system, while the automatic test is in progress, that test is automatically cancelled.
3.9.4
Replace Sensor
This option refers only to the VIEW sensor. If a VIEW sensor is removed from an existing operational
loop, or communication with the panel is broken for a minimum of 30 seconds, recalibration will take
place automatically.
Note: If a VIEW sensor is removed and cleaned or replaced with a new one, you should wait at
least 30 seconds after removal before replacing it.
VIEW sensors can also be recalibrated manually, either individually or an entire loop or panel at once.
Press key’0’ followed by key ‘2’ or ‘3’ (depending on other configuration options). You are then prompted
for a ‘configuration’ passcode. Enter the passcode and the panel now displays:
0 = Individual/ 1= Entire Loop:
If you press ‘0’ the panel now displays:
Select replaced sensor:
Choose from ZONE no.: (0=ALL)? 0
10