Pittway ID1002/16 Скачать руководство пользователя страница 2

997-340-001, Issue 8
April 1998

ID1000 Series Operating Manual

Installation Precautions

Adherence to the following will aid in problem-free installation and
a system with long-term reliability:

WARNING

 - Several different sources of power can be connected

to this fire alarm control panel.  Disconnect all sources of power
before servicing. Control unit and associated equipment may be
damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt
to install, service, or operate this unit until this manual is read and
understood.

CAUTION - 

System Re-acceptance Test after Software Changes:

To ensure proper system operation, this product must be tested
after any programming operation or change in site-specific
software. Reacceptance testing is also recommended after any
change, addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at
least 10% of initiating devices that are not directly affected by the
change, up to a maximum of 50 devices, should also be tested
and proper system operation verified.

This system  may operate over the range of 0-49

O

C and at a

relative humidity of 90% RH (non-condensing) at 30

C. However,

the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a nominal
room temperature of 5-35

O

 C.

Fire Alarm System Limitations

An automatic fire alarm system - typically made up of smoke
detectors, heat detectors, call points, audible warning devices,
and a fire alarm control with remote notification capability can
provide early warning of a developing fire. Such a system, however,
does not assure protection against property damage or loss of
life resulting from a fire.

Any fire alarm system may fail for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach
the detectors such as in chimneys, in walls, or roofs, or on the
other side of closed doors.

Smoke detectors also may not sense a fire on another level or
floor of a building. A second floor detector, for example, may not
sense a first floor or basement fire. Furthermore, all types of smoke
detectors - both ionisation and photoelectric types, have sensing
limitations. No type of smoke detector can sense every kind of
fire caused by carelessness and safety hazards like smoking in
bed, violent explosions, escaping gas, improper storage of
flammable materials, overloaded electrical circuits, children playing
with matches, or arson.

Audible warning devices such as bells  may not alert people if
these devices are located on the other side of closed or partly
open doors or are located on another floor of a building.

A fire alarm system will not operate without any electrical power.
If mains power fails, the system will operate from standby batteries
only for a specified time.

Verify that wire sizes are adequate for all initiating and indicating
device loops. Most devices cannot tolerate more than a 10% I.R.
drop from the specified device voltage.

Like all solid state electronic devices, this system may operate
erratically or can be damaged when subjected to lightning induced
transients.  Although no system is completely immune from
lightning transients and interferences, proper grounding will reduce
susceptibility. 

Notifier does not recommend the use of overhead

or outside aerial wiring due to the increased susceptibility to nearby
lightning strikes.

Disconnect mains power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure.  When possible, make all
cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, and
printed circuit board location.

Do not tighten screw terminals more than 1Nm. Over tightening
may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.

This system contains static-sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. Use static-
suppressive packaging to protect electronic assemblies removed
from the unit.

Follow the instructions in the installation, operating, and
programming manuals.  These instructions must be followed to
avoid damage to the control panel and associated equipment.

Rate-of-Rise heat detectors may be subject to reduced sensitivity
over time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection
specialist.

While installing a fire alarm system may make lower insurances
rates possible, it is not a substitute for fire insurance!

Equipment used in the system may not be technically compatible
with the control. It is essential to use only equipment listed for
service with your control panel.

The most common cause of fire alarm malfunctions, however,
is inadequate maintenance. All devices and system wiring should
be tested and maintained by professional fire alarm installers
following written procedures supplied with each device. System
inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of
all inspections should be kept.

Содержание ID1002/16

Страница 1: ...ATING MANUAL Ref 997 340 001 Issue 8 April 1998 NOTIFIERLimited CharlesAvenue BurgessHill WestSussex RH15 9UF Tel 01444 230300 Fax 01444 230888 Note This manual applies only to panels with software ve...

Страница 2: ...ammable materials overloaded electrical circuits children playing with matches or arson Audible warning devices such as bells may not alert people if these devices are located on the other side of clo...

Страница 3: ...ntrol Output Test CMX Modules 8 3 9 2 2 Control Output Test Local Sounder Circuits 9 3 9 3 Sensor Automatic Test 10 3 9 4 Replace sensor 10 3 10 Setting the Clock 11 3 11 Display and or Log Device Dat...

Страница 4: ...Status 28 6 1 10 Panel PRINTER Control Status 28 7 MENU MAPS 29 Figure 7 1 Top Level Menu Options 29 Figure 7 2 TEST Menu Options 30 Figure 7 3 SET CLOCK Menu Option 30 Figure 7 4 MASK UNMASK Menu Opt...

Страница 5: ...using the pushbuttons on the front of the panel alone many of them can on some installations also be carried out by use of function keys on a remote VDU terminal or by operation of remote switches con...

Страница 6: ...emises is achieved or at the direction of an authorised person the Alarm sounders may be silenced by pressing the SILENCE SOUNDERS pushbutton If there are any delayed operations for which the timer ha...

Страница 7: ...as SYSTEM FAULT xx where xx is a number of up to 2 digits e Operation of the fault transfer relay for automatic alert to a service centre 2 6 FAULT Recommended Operator Actions a Press MUTE INTERNAL S...

Страница 8: ...ogramming Manual for more details 997 340 000 and 997 340 003 Pressing any disabled function key will cause an internal beep and a refresh of the display 3 2 Top Level Display Except when some operato...

Страница 9: ...recorded as missing Press ENTER at any time when the display is scrolling and the system if appropriate displays Log each missing device individually Y N If YES is pressed all the individual devices i...

Страница 10: ...Press this pushbutton or the appropriately labelled VDU key or remote switch if available to reset the system completely except after an EVACUATE operation Provided that no FIRE PRE ALARM or FAULT co...

Страница 11: ...walk round test of sensors or MCPs select 0 and see Section 3 9 1 To carry out a Control Output test select 1 and see Section 3 9 2 To perform the daily or weekly sensor automatic test select 2 and se...

Страница 12: ...e test condition is removed In the case of a Manual Call Point test the appropriate sounder outputs are activated according to the specified test requirements either for approximately one second or fo...

Страница 13: ...ENTER details of the existing module nearest in number to what you typed are shown and you may then continue to step up or down from that point Press ENTER a second time to finally select the module N...

Страница 14: ...but with the message Weekly automatic test in progress or Daily automatic test in progress on line 2 of the display this message also appears when the test is in progress at the scheduled time for as...

Страница 15: ...ate on which it had been operating or at the time when the clock was last reset whichever was the later Press Pushbutton 3 The clock display will be frozen and the display will show SETTING CLOCK date...

Страница 16: ...Dump The option required is 0 The display then shows 0 Sensors 1 Modules Press the appropriate pushbutton depending on whether you want to inspect Analogue sensors or Monitor Control modules If after...

Страница 17: ...andard display press CANCEL on VDU press ctrl X Alternatively you may continue to use the up and down arrows to examine other devices data The LED pulsing option is only available from the panel keypa...

Страница 18: ...Confirm Y N to which YES should be answered to complete the set up NO to cancel the whole procedure The maximum store capacity depends on the available memory and if another sensor is already being l...

Страница 19: ...rinted This is the only occasion on which a list of devices at another panel can be obtained Note that only one of the above special options at a time can be selected i e you cannot print out selectiv...

Страница 20: ...flash Use the and arrows in the same way to step back and forward an hour at a time times will be rounded to the nearest hour When you press ENTER again the first event which occurred after the selec...

Страница 21: ...ed after a set time out or at certain times of the day Time of day controlled MASK and UNMASK are possible with software versions 3 32 and 1 32 using two new Control Matrix types TRUE and FALSE Note T...

Страница 22: ...l then displays one of the following depending on your selection UNMASK ALL devices zone n Y N or MASK SENSORS in zone n Y N or MASK ALL inputs zone n Y N or MASK ALL devices zone n Y N If you choose...

Страница 23: ...that it refers to the Slave panel Then the system displays 0 Unmask 1 Mask Press 0 or 1 as required Unlike when masking local zones there is no option to specify whether sensors all inputs or input a...

Страница 24: ...requests you to choose between temporary and permanent mode as described in Section 3 14 1 See that section for further details 3 14 3 Mask and Unmask Complete Zone via Remote Switch This function is...

Страница 25: ...ation 4 1 MUTE Internal Sounder Press Function Key F10 The same MUTE operations as defined in Section 3 3 are carried out but there is no scrolling display and no review of other events outstanding 4...

Страница 26: ...puts without the need for access to the panel Operate the switch as indicated so as cause the sounders or other outputs to operate in the pre programmed pattern Release the switch so as to switch off...

Страница 27: ...ditions 6 1 1 Panel NORMAL Status This is the condition of the panel when it is operational and there are no uncleared FIREs or FAULTs no part of the system is MASKED and no TESTing or CONFIGURATION i...

Страница 28: ...me of alarm location date time of alarm plus indication as to whether any further alarms exist indicated by MORE PRESS or Internal sounders if not accepted Fire sounder high pitched on STEADY if accep...

Страница 29: ...ed by MORE PRESS or Internal sounders Fire sounder high pitched on intermittently one bleep every 2 minutes Circuits Controlled Internally and External Devices Programmed function 6 1 4 Panel FAULT St...

Страница 30: ...on all other sensors and modules should either give short pulses or be OFF altogether 6 1 5 Panel DEVICES MASKED Status This is indicated when some or all of the sensors or modules of the system have...

Страница 31: ...dules those for which the control output is ON also be on STEADY The LEDs of all other sensors and modules should either give short pulses or be OFF altogether 6 1 7 Panel TEST Status This is the cond...

Страница 32: ...y identical to the NORMAL status except that a special option has been selected by the authorised engineer to partially inhibit the functioning of the fault buzzer Operation of the FIRE internal sound...

Страница 33: ...ted in Figures 7 1 to 7 5 Refer to the ID1000 Series Programming Manual 997 340 003 for the menu map on programming functions accessed through pressing 4 on the numeric keypad Note Tinted boxes are us...

Страница 34: ...997 340 001 Issue 8 April 1998 ID1000 Series Operating Manual Figure 7 2 TEST Menu Options Figure 7 3 SET CLOCK Menu Option 30...

Страница 35: ...997 340 001 Issue 8 April 1998 ID1000 Series Operating Manual Figure 7 4 MASK UNMASK Menu Options Figure 7 5 LOG DISPLAY Menu Options 31...

Страница 36: ...ey are supervising Possible types are for input MMX types MCP Manual call point MON General monitoring function SPRK Sprinkler switch monitoring AUX Auxiliary non latching input For output CMX types C...

Страница 37: ...olts supply failed or voltage outside limits 36 Auxiliary 24 volts supply failed or voltage outside limits 37 Fire Transfer relay monitored fault 38 Fault Transfer relay monitored fault 39 Evacuate Tr...

Страница 38: ...ally at the panel Ferrite suppressors are fitted to loop wiring at the control panel 32 This fault indicates that the peripheral unit has not responded to the enquiry code sent or the link to the thir...

Страница 39: ...ult occurs change the PSU PCB 50 This fault code indicates a short circuit fault on sounder circuit 2 wiring Disconnect the wiring and use a meter to locate the fault 51 This fault code indicates a sh...

Отзывы: