NEVER LEAVE HEATER UNATTENDED WHILE BURNING 

OR WHILE CONNECTED TO A POWER SOURCE

© 2017, Pinnacle Climate Technologies, Inc. 

Kerosene Forced Air Heater User’s Manual 

Maintenance

Service (Continued):
SPARK PLUG:

Clean and re-gap every 600 hours of operation, or 

replace as needed. After removing the spark plug, 

clean the terminals with a wire brush. Re-gap the 

terminals to 0.140” (3.5mm) See Figure 5.

PHOTOCELL:

The photocell should be cleaned using a cotton 

swab dipped in alcohol or water at least once per 

heating season, or more depending on conditions. 

See Figure 6.

PUMP PRESSURE:

While heater is operating, turn adjusting screw 

clockwise to increase, counter-clockwise to 

decrease pressure. Correct pump pressure is as 

follows: 

Model Number

Pump Pressure

45-KFA

3.0 PSI

75T-KFA

4.2 PSI

135T-KFA

5.5 PSI

175T-KFA

7.5 PSI

190T-KFA

8.5 PSI

215T-KFA

9.0 PSI

Tolerance ± 10%

NOZZLES:

Nozzles should be cleaned or replaced at least 

once per heating season. Contaminated fuel could 

make this necessary immediately. To clean dirt 

from nozzle, blow compressed air through nozzle 

front. It may be necessary to soak the nozzle in K-1 

kerosene to loosen any dirt particles.

Figure 5

Ignitor Wire

Spark Plug

Gap

Burner Head

Figure 6

X

X

Photocell

Photocell lens

Photocell 

Wire

8

Figure 8

Adjusting Screw

Pressure Valve

Figure 7

Nozzle

Nozzle Face

Burner Head

Содержание REMINGTON REM-135T-KFA-O

Страница 1: ...to Ventilation on Page 5 FACTORY ID 001 Safety Information FIRE BURN INHALATION AND EXPLOSION HAZARD Keep combustibles such as building materials paper or cardboard a safe distance away from the heate...

Страница 2: ...use for temporary heating of buildings under construction alteration or repair Direct fired means that all of the combustion products of the heater enter the heated space This appliance is rated at 98...

Страница 3: ...ls away from this heater Minimum Clearance From Combustibles 45 190T KFA 215T KFA Top 4 ft 4 ft Sides 4 ft 4 ft Front 8 ft 10 ft ALWAYS locate heater on a stable and level surface If your heater is eq...

Страница 4: ...Manual 3 Wiring Diagrams 45 KFA 75T 215T KFA Assembly Instructions What s In The Box Models 45 KFA 75T KFA Remove the heater and all packaging materials from the shipping carton Note Save the box and...

Страница 5: ...lace heater on wheel support and line up holes on the fuel tank lip 5 Attach front handle with 2 long screws 50 mm and 2 nuts through the second hole from the front on both sides of the tank lip and w...

Страница 6: ...R use kerosene that has been stored from one season to the next Kerosene deteriorates over time OLD KEROSENE WILL NOT BURN PROPERLY IN THIS HEATER NOTE Kerosene should only be stored in a blue contain...

Страница 7: ...temperature display will indicate the following When the temperature is less than 0 F the display says LO When the temperature is more that 99 F the display says HI Between 0 F and 99 F the display s...

Страница 8: ...starting the heater FUEL FILTER The fuel filter should be cleaned at least twice per heating season Clean the filter by rinsing it in clean K 1 Kerosene Contaminated fuel could make cleaning the fuel...

Страница 9: ...ESSURE While heater is operating turn adjusting screw clockwise to increase counter clockwise to decrease pressure Correct pump pressure is as follows Model Number Pump Pressure 45 KFA 3 0 PSI 75T KFA...

Страница 10: ...proper spacing with rotor 1 Fill tank with fresh kerosene 2 Adjust pump pressure 3 Clean replace spark plug 4 Clean replace fuel filter 5 Clean replace nozzle 6 Rinse fuel tank with clean fresh kerose...

Страница 11: ...POWER SOURCE 2017 Pinnacle Climate Technologies Inc Kerosene Forced Air Heater User s Manual 10 14 11 13 8 12 9 30 26 3 16 2 4 6 1 7 22 24 17 18 19 21 30 20 15 41 33 35 36 29 28 5 32 31 25 27 38 37 3...

Страница 12: ...21 0510 70 021 0520 70 021 0520 18 Pump Body 70 020 0101 70 020 0101 70 020 0101 70 020 0401 70 020 0401 19 Rotor Kit 70 022 0100 70 022 0100 70 022 0100 70 022 0200 70 022 0200 20 End Pump Cover 70 0...

Страница 13: ...If Pinnacle Climate Technologies Inc finds the item to be in normal operating condition or not defective the item will be returned freight collect This Limited Warranty is in lieu of all other expres...

Страница 14: ...1 Industrial Blvd 101 Sauk Rapids MN 56379 USA Toll Free 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Email info pinnacleclimate com 2017 Pinnacle Climate Technologies Inc...

Страница 15: ...n de seguridad PELIGRO DE INCENDIO QUEMADURAS INHALACI N Y EXPLOSI N Mantenga los combustibles como materiales de construcci n papel o cart n a una distancia prudente del calentador seg n lo recomien...

Страница 16: ...efacci n temporal de edificios en construcci n modificaci n o reparaci n Fuego directo significa que todos los productos de combusti n del calentador ingresan en el espacio calentado Este aparato tien...

Страница 17: ...a todos los materiales combustibles lejos de este calentador Separaci n m nima entre el calentador y materiales combustibles 45 190T KFA 215T KFA Superior 4 pies 1 2 m 4 pies 1 2 m Lados 4 pies 1 2 m...

Страница 18: ...NTROL DE TEMP FOTOC LULA SENSOR DE AMBIENTE NEGRO NEGRO NEGRO NEGRO NEGRO NEGRO NEGRO NEGRO NEGRO TIERRA TIERRA VERDE VERDE BLANCO BLANCO BLANCO ROJO AZUL NEGRO NOTA Los modelos 125T 135T 175T 190T 21...

Страница 19: ...orte de las ruedas y alinee los orificios en el reborde del tanque de combustible 5 Fije el asa delantera con 2 tornillos largos 50 mm y 2 tuercas a trav s del segundo orificio desde el frente en ambo...

Страница 20: ...enado de una temporada a la siguiente El queroseno se deteriora con el tiempo EL QUEROSENO VIEJO NO SE QUEMAR ADECUADAMENTE EN ESTE CALENTADOR NOTA El queroseno debe almacenarse nicamente en un conten...

Страница 21: ...talla mostrar LO Cuando la temperatura es superior a 99 F 37 2 C la pantalla mostrar HI Entre 0 F 18 C y 99 F 37 2 C el indicador mostrar la temperatura actual Apagado Reencendido del calentador Para...

Страница 22: ...FILTRO DE COMBUSTIBLE El filtro de combustible debe limpiarse al menos dos veces por cada temporada de calefacci n Enjuague el filtro con queroseno K 1 limpio El combustible contaminado podr a hacer q...

Страница 23: ...A Mientras el calentador est funcionando gire la v lvula de seguridad hacia la derecha para aumentar la presi n o hacia la izquierda para disminuirla A continuaci n se muestra la presi n correcta de l...

Страница 24: ...resi n de la bomba 3 Limpie o reemplace la buj a 4 Limpie o reemplace el filtro de combustible 5 Limpie o reemplace la boquilla 6 Enjuague el interior del tanque con queroseno nuevo y limpio 7 Inspecc...

Страница 25: ...E DE ALIMENTACI N 2017 Pinnacle Climate Technologies Inc Manual del usuario del calentador de aire forzado de queroseno 10 14 11 13 8 12 9 30 26 3 16 2 4 6 1 7 22 24 17 18 19 21 30 20 15 41 33 35 36 2...

Страница 26: ...21 0500 70 021 0500 70 021 0510 70 021 0520 70 021 0520 18 Cuerpo de la bomba 70 020 0101 70 020 0101 70 020 0101 70 020 0401 70 020 0401 19 Juego de rotor 70 022 0100 70 022 0100 70 022 0100 70 022 0...

Страница 27: ...le Climate Technologies Inc descubre que el art culo est en condiciones normales de funcionamiento o que no est defectuoso se devolver el art culo con el flete por cobrar Esta Garant a Limitada reempl...

Страница 28: ...dustrial Blvd 101 Sauk Rapids MN 56379 EE UU Llamada sin costo 866 676 1989 Fax 320 251 2922 Web www remingtonheater com Correo electr nico info pinnacleclimate com 2017 Pinnacle Climate Technologies...

Отзывы: