Captain 6 Installation Guide
33
5.5.2
AC failure response
See section 3.2.4 for programming instructions of the parameters bar.
Par.
Onscreen When setting to “+”
S
Siren
The siren will be triggered
P
Communic. The alarm will be reported to the Monitoring Station and the end user
via the phone, and to the Monitoring Station via the Radio too.
B
Buzzer
keypad buzzer activated
G
PGM
The PGM output will be triggered
5.5.2.1
Response delay time
Set the AC failure report delay time in minutes (up to 250).
5.5.3
Battery failure response
See section 3.2.4 for programming instructions of the parameters bar.
Par.
Onscreen
When setting to “+”
S
Siren
The siren will be triggered
P
Communic.
The alarm will be reported to the Monitoring Station and the end
user via the phone, and to the Monitoring Station via the Radio too.
B
Buzzer
The keypad chime will be activated
G
PGM
The PGM output will be triggered
5.5.4
Phone line failure response
See section 3.2.4 for programming instructions of the parameters bar.
Par.
Onscreen
When setting to “+”
S
Siren
The siren will be triggered
P
Communic.
The alarm will be reported to the Monitoring Station and the end user
via the phone, and to the Monitoring Station via the Radio too.
B
Buzzer
The keypad chime will be activated
G
PGM
The PGM output will be triggered
5.5.4.1
Response delay time
Set the phone line failure report delay time in minutes (up to 250).
5.5.5
Zone fail response
Zone fail can occur only in EOL resistor loop zones.
See section 3.2.4 for programming instructions of the parameters bar.
Par.
Onscreen
When setting to “+”
S
Siren
The siren will be triggered
P
Communic.
The alarm will be reported to the Monitoring Station and the end user
via the phone, and to the Monitoring Station via the Radio too.
B
Buzzer
The keypad chime will be activated
G
PGM
The PGM output will be triggered