First commissioning
Operating Manual PSEN sc L 3/5 series
1005056-EN-01
| 67
Click on the arrow
. The next window is opened:
Output configuration
. The number
of OSSD pairs is already selected.
4. Select
Warning zone
= 0.
If
Warning zone
= 0, the warning zone is deselected. The output Pin 1 is automatically
set to NOFUNCTION. The output cannot be used.
Select
Muting
=
Activated
The outputs Pin 5 and 6 are reserved for OSSD 1 and OSSD 2 and cannot be changed.
Click on the arrow
. The next window
Configure zone sets
is opened.
5. Click on the arrow
. The next window
Configure zone sets
is opened.
Zone set = 1 is already selected. Further settings are not required.
Click on the arrow
. The next window
Input configuration
is opened
6. For
Restart
select the value
Automatic
and define the
Recovery time
(min. 200 ms,
max. 60000 ms).
Select the
Muting type
and specify the value for
Muting activation delay [ms]
.
For
Muting type
=
L muting
a factor can be specified for an increase of the activation
delay.
If necessary, specify a value for time monitoring of the muting function (
Time exceeded
[min] (0 = no time exceeded)
)
In
Input wiring
select the PINs to which the muting sensors are connected. For dy-
namic activation of the muting state,
Activate muting 1
must also be assigned to a
PIN.
CAUTION!
Risk of injury due to loss of the safety function.
If time monitoring for the muting function is set to ∞, the muting function is
not cancelled until the muting sensors are no longer active.
This setting does not comply with the specifications of EN ISO 61496-1.
– Make sure that sustained muting is detected.
7. Click on the arrow
. The next window
Configure detection capability
is opened.
8. Under
Multiple evaluation
, define the number of consecutive scans needed for detec-
tion.
Increasing the number of consecutive scans will increase the response time of the
safety laser scanner.
9. Select the
detection capability [mm]
for this safety laser scanner. Define the value for
Safety zone
or for
Warning zone
.
Please note:
With a resolution of 40 mm, the range of the safety zone expands to 3 m, and the range
of the warning zone expands to 22 m.
10. Select
Dust filter level
(level 1 = low, level 3 = high).
A higher level of dust filtering requires a longer safety distance.