Project configuration
Operating Manual PSEN sc L 3/5 series
1005056-EN-01
| 43
If material is transported from the left-hand side, the cycle is re-
versed. The output side becomes the input side and the flow
starts with the second muting sensor on the output side.
5.13.4
Dynamic muting
When
Activate muting
is selected for one of the inputs 3, 9, 10 or 11, muting can be activ-
ated and deactivated dynamically.
}
Conditions for the occurrence of muting
– One of the inputs 3, 9, 10 or 11 is connected to a controller and it receives a high sig-
nal from there when muting is to be activated
– When configuring the inputs,
Activate muting
is configured for this input in
PSENscan Configurator
– The first sensor has detected a conveyed material and the second sensor also detec-
ted it max. 4 s later
or
the first sensor and the second sensor detected conveyed ma-
terial simultaneously
5.14
Override
The override function can be used for the three types according to the timing diagrams.
}
Single-channel pulses
}
Activation by rising edge
}
Activation by rising signal (only when using the 12-pin connection)
Protective zone
Status
Override
Single-channel
Pulse
On
Off
On
Off
24 V
0 V
t
2 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
Fig.: Timing diagram for override function single-channel pulses