Installation
Operating Manual PNOZ m ES 14DO
1004299-EN-02
11
5
Installation
5.1
General installation guidelines
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Fit the safety system to a horizontal mounting rail. The venting slots must face upward
and downward. Other mounting positions could damage the safety system.
}
Use the locking elements on the rear of the unit to attach it to a mounting rail.
}
In environments exposed to heavy vibration, the unit should be secured using a fixing
element (e.g. retaining bracket or end angle).
}
Open the locking slide before lifting the unit from the mounting rail.
}
To comply with EMC requirements, the mounting rail must have a low impedance con-
nection to the control cabinet housing.
}
The ambient temperature of the PNOZmulti units in the control cabinet must not exceed
the figure stated in the technical details, otherwise air conditioning will be required.
NOTICE
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure against discharge
before touching the product, e.g. by touching an earthed, conductive sur-
face or by wearing an earthed armband.
5.2
Dimensions in mm
22,5
(0.88")
5.3
Connecting the base unit and expansion modules
Connect the base unit and the expansion modules as described in the operating manuals
for the base modules.
}
The terminator must be fitted to the last expansion module
}
Install the expansion module in the position configured in the PNOZmulti Configurator.