PKB-M, PKB-MS Operating Manual
16
Operation
Peak Cur
XXX.XA
Peak current
XXX.X
Peak value of the braking current when the brake contactor
energises or de-energises (switching current of the brake
contactor)
So as not to damage the free wheel diode, the switch-on current should
not exceed 100 A.
INFORMATION
To reduce the switch on current, increase safety time t
v1
.
To reduce the switch off current, increase safety time t
v3
. This increases
the life of the brake contactor.
N XX.XA
A YY.YA
Braking current
XX.X
set braking current
YY.Y
measured effective value of the braking current
Max XXX#
A YYY# Z
Standstill threshold
Only on units with standstill detection
XXX
highest level of the standstill signal
YYY
current level of the standstill signal
Z
1, 2, 3 or 4; Step in the control logic (see standstill menu and
sub-menu)
N XXX°Ci
A YYY°Ci
Heatsink temperature
XXX
set maximum value of the heatsink temperature
YYY
current value of the heatsink temperature
N XXXk
Ω
e
A YYYk
Ω
e
Motor temperature
XXX
set maximum value of the external PTC-thermistor
YYY
current value of the external PTC-thermistor