Interfaces
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
| 48
5.3
Ethernet interface
Two free switch ports are provided as Ethernet interfaces via an internal autosensing
switch. The autosensing switch automatically detects whether data transfer is occurring at
10 Mbit/s or 100 Mbit/s.
INFORMATION
The connected subscribers must support the autosensing/autonegotiation
function. If not, the communication partner must be set permanently to "10
Mbit/s, half duplex".
The switch's automatic crossover function means there is no need to distinguish on the
connection cable between patch cable (uncrossed data line connection) and crossover
cable (crossover data line connection). The switch automatically creates the correct data
line connection internally. Patch cable can therefore be used as the connection cable for
end devices as well as cascading.
Both Ethernet interfaces use RJ45 technology.
The Ethernet interface is configured in the PAS4000 (for a description see the chapter en-
titled "Hardware Configuration" -> "Configuration of the PSSu Modules" -> "Configure PSSu
Modules" -> "Configure Special Modules" -> "PSSu K F FAU" in PAS4000's online help).
Ethernet Interface
RJ45 socket
8-pin
PIN
Standard
Crossover
8 1
1
TD+ (T)
RD+ ()
2
TD- (Transmit-)
RD- (Receive-)
3
RD+ ()
TD+ (T)
4
n.c.
n.c.
5
n.c.
n.c.
6
RD- (Receive-)
TD- (Transmit-)
7
n.c.
n.c.
8
n.c.
n.c.