Function description
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
| 19
Characteristic for dual-pole outputs: Output capacitance C dependent on load current
2
4
6
8
10
0
0,4
0,6
0,8
1,2
1,6
2
2,4
2,8
3,2
3,6
C [µF]
I [A]
4.4.3
Notes
WARNING!
When wiring an output with capacitance it is essential to note the pulse dur-
ation, repetition period and scan time of the power-up test, otherwise the
load may switch on unintentionally.
}
For applications in accordance with Category 4, PL e and SIL 3, detection of shorts
between contacts must be guaranteed either via the on/off test or through other meas-
ures (e.g. asynchronous switching). A short between contacts must be simulated during
commissioning.
4.5
Fast shutdown
The module switches the outputs off immediately when:
}
The signal from the protected field evaluation (OSSD) switches from 1 to 0 (protected
field violated).
}
The signal for dynamic muting (MUTE) switches from 1 to 0. (Object interrupts advance
measuring field.)
}
The signal switches from 1 to 0 at one of the input pairs I00 and I01, I02 and I03. The
edge used to trigger the fast shutdown can be configured (see
).