Function description
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
| 15
Detection of shorts across contacts
}
The test pulses are used to detect shorts between inputs. Shorts between inputs are de-
tected when the test pulses are different (test pulse T00, test pulse T01).
}
Only the module's test pulses may be used to detect shorts.
}
The module's test pulses may not be used to detect shorts between inputs on other mod-
ules.
}
Shorts between inputs of the same module with the same test pulses will not be detected.
}
Test pulses can be switched on or off.
}
Test pulses are switched on in the default setting.
}
When test pulses are switched off, the periphery supply is constantly available at the test
pulse outputs.
4.4
Outputs
4.4.1
Single-pole outputs
}
2 single-pole digital outputs
Output test
}
Outputs that are switched on are checked via regular off tests.
– Test pulses for outputs that are switched on: see
– Outputs that are switched on are switched off for the duration of the test pulse.
– The load must not switch off because of the test.
}
Outputs that are switched off are checked via regular on tests.
– Test pulses for outputs that are switched off: see
– Outputs that are switched off are switched on for the duration of the test pulse.
– The load must not switch on because of the test.
Testing for shorts
}
A test is regularly carried out to check for shorts between the outputs.
Excluding individual outputs from the output test:
}
If a plant is particularly sensitive to the test pulses, the output test may be switched off for
individual outputs.
}
The test must be replaced by other measures, depending on the safety requirement.
}
When test pulses are switched off:
– The correct switch status is always checked.
– The output's ability to switch will not be detected until the next time the output is
switched on/off.