Function description
Operating Manual PSSu K F FAU B, PSSu K F FAU P
1003434-EN-05
| 22
}
Receiver position
}
IP address (default IP address: 169.254.1.2)
Further information is available in PAS4000's online help.
The input filter time can be configured in increments of 100 µs. The input filter time de-
pends on the edge configured for fast shutdown. For each input filter time that is con-
figured, there are two values each for the rising and the falling edge:
}
Safely filtered out; indicates which signals are safely filtered out.
}
Safely detected; indicates which signals are safely detected.
INFORMATION
If the input filter times are short, the module's electromagnetic immunity to-
wards electromagnetic faults will deteriorate.
NOTICE
Signal times are only guaranteed if input pairs (I00 and I01, I02 and I03) are
used.
Configured in-
put filter time
(FZ)
Fast shutdown with rising edge
Fast shutdown with falling edge
Safely filtered
out signal time
(µs)
Safely detected
signal time (µs)
Safely filtered
out signal time
(µs)
Safely detected
signal time (µs)
200
13
100
10
200
300
30
200
110
300
400
130
300
210
400
500
230
400
310
500
…
FZ - 270
FZ -100
FZ - 190
FZ
…
…
…
…
…
…
…
…
…
…
3100
2830
3000
2910
3100
3200
2930
3100
3010
3200
3300
3030
3200
3110
3300