Speed I
= 200 m³/h
Speed II
= 300 m³/h
Speed III
= 400 m³/h
with external pressure increase of 100
Pa and integrated sound absorption
splitter on the exhaust air side
Remark: Tolerances ± 2 dB for acoustic
data
5.4 ACOUSTIC SPECIFICATIONS
Measuring
point
Housing emission
Outdoor air
Supply air
Exhaust air
Extract air
Fan speed
I
II
III
I
II
III
I
II
III
I
II
III
I
II
III
63 Hz
L
w
in dB
45
47
49
65
67
69
59
65
72
64
66
68
62
64
66
125 Hz
44
44
44
60
60
60
55
58
61
60
61
62
56
57
57
250 Hz
44
47
49
60
61
62
49
52
55
60
62
63
57
58
59
500 Hz
35
37
40
45
50
55
37
43
48
43
50
57
44
49
54
1000 Hz
31
32
33
31
35
39
25
31
37
31
36
41
30
35
39
2000 Hz
26
29
31
27
32
37
18
25
31
32
37
43
27
32
36
4000 Hz
24
28
31
21
26
32
14
20
26
30
35
40
16
21
26
8000 Hz
19
21
22
13
17
21
11
13
16
17
23
30
11
13
14
Total
L
WA
in dB(A)
39
41
44
53
55
57
44
48
53
53
55
60
50
51
55
6 Operator control unit
The settings made on the ventilation unit
are performed via an operator control
unit. Control and operation of the venti-
lation unit is performed via the „PI-HMI“
control unit for surface mounting.
The touchscreen makes performing set-
tings simple. All important operating
data are displayed.
The control unit is normally
installed in the living area
and should be suitably positi-
oned. Thermal source areas, radiators,
direct sunlight etc. have to be avoided on
account of their temperature influence!
6.1 GENERAL INFORMATION
6.2 OPERATOR CONTROL UNIT
“PI-HMI“
PI-HMI is a touchscreen panel with
user-friendly graphical user interface
specially developed for controlling venti-
lation systems. The panel communicates
with the PI Air2 system via a Modbus
interface, ensuring easy installation.
Product:
PI-HMI
Type:
3,5“ touchscreen panel