ILC 330.../350...
90
PHOENIX CONTACT
6959_en_07
A 3
Connecting unshielded cables
Unshielded cables are used to connect the I/O devices and the supply voltage to the Inline
controller.
Connect these cables to the relevant Inline connectors using the spring-cage connection
method. You may connect cables with a connection cross section of 0.2 mm
2
to 1.5 mm
2
(24 - 16 AWG).
Figure A-1
Connecting unshielded cables
Wire the connectors according to your application.
When wiring, proceed as follows:
•
Strip 8 mm off the cable.
•
Push a screwdriver into the actuation shaft of the appropriate terminal point (Figure A-1,
A) so that you can insert the wire into the spring opening.
Phoenix Contact recommends the SFZ 1-0,6x3,5 screwdriver (Order No. 1204517).
•
Insert the wire (Figure A-1, B). Remove the screwdriver from the opening. This clamps
the wire.
After installation, the wires and the terminal points should be marked.
Inline wiring is normally done without ferrules. However, it is possible to use ferrules. If
using ferrules, make sure they are properly crimped.
B
ig
ita
lIn
p
1
A
6452C032
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...