ILC 330.../350...
84
PHOENIX CONTACT
6959_en_07
Network interface
Type
Ethernet
10Base-T and 100Base-TX
Speed
10 Mbits (10Base-T), 100 Mbits (100Base-TX)
half duplex, full duplex, auto negotiation
Connection technology
CAT5 twisted pair cable
RJ45 socket
This speed cannot be set manually. It is set automatically by means of auto negotiation.
Inline local bus
Interface
Inline local bus
Electrical isolation
No
Number of devices
63, maximum, limited by the maximum current consumption from the
communications power and analog supply
INTERBUS remote bus
Interface
Inline data jumper
Electrical isolation
Yes
Number of devices
See technical data for “INTERBUS” on page 83 and “Number of devices in
the INTERBUS system” on page 83.
Diagnostic interface
Connection technology
6-pos. Mini-DIN socket (PS/2)
Interface type
RS-232
Transmission speed
9600 baud
Electrical isolation
No
PROFINET functions (ILC 330 PN / ILC 350 PN)
Device function
PROFINET controller
Conformance class
B
Performance class
RT
Number of PROFINET devices
100, maximum, depending on the update time for inputs and outputs
Update time for inputs and outputs
1 ms, minimum
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...