ILC 330.../350...
34
PHOENIX CONTACT
6959_en_07
2.13
INTERBUS
2.13.1
Local bus
The local bus is automatically created by directly connecting I/O modules to the Inline
controller.
2.13.2
Remote bus
Connect the remote bus to the Inline controller using one of the following branch terminals
(e.g., IBS IL 24 RB-T-PAC).
Both the connected remote bus and the connected remote bus branches can be further
branched. Up to 16 bus levels (i.e., 15 branches) are permitted.
Figure 2-20
Bus configuration with remote bus and local bus
Observe the information in the “Configuring and installing the INTERBUS Inline product
range” user manual IB IL SYS PRO UM E when creating an Inline system (local bus
and/or remote bus).
The IB IL 24 FLM-PAC or IB IL 24 FLM MULTI-PAC terminals can only be diagnosed to a
limited extent in the local bus of the ILC 3xx.
For unlimited diagnostics, it is recommended that you use IB IL 24 FLM-PAC or IB IL 24
FLM MULTI-PAC terminals at the IBS IL 24 RB-T-PAC terminal.
The
first branch terminal
must be placed directly after the Inline controller. In terms of
topology, it opens a
remote bus
.
If
additional branch terminals
are used after the first branch terminal, they must be
installed directly one after the other (see also notes in the terminal-specific data sheet). In
terms of topology, the additional branches are
remote bus branches
with the branch
terminal being the first device in the corresponding remote bus branch.
Please note that isolated connection and disconnection is only possible with remote bus
branch and local bus interfaces. Isolated connection and disconnection is not possible
with the remote bus.
1
PLC
RUN
FAIL
RUN / PROG
MRESET
STP
INLINE CONTROL
ILC 350 ETH
Ord.No.: 27 37 203
IL
RDY / RUN
BSA
FAIL
PF
PRG
ETH
LNK
ACT
100
10/100
RESET
1
2
1
2
3
4
1
2
3
4
1
2
US
UM
UL
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I3
I4
I1
I2
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
Q2
Q3
Q4
E
Q1
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I9
I10
I11
I12
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I5
I6
I7
I8
RC
RD
D
RB-T
LD
Remote bus
Ethernet
6959B011
Local bus
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...