ILC 330.../350...
86
PHOENIX CONTACT
6959_en_07
Realtime clock
Accuracy
1 min./week, maximum
Power reserve
120 days
Ambient conditions
Degree of protection
IP20 (EN 60529:1991)
Permissible temperature (operation)
-25°C to +55°C
Permissible temperature (storage/transport)
-25°C to +85°C
Permissible humidity (operation/storage/transport)
10% to 95%, according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 106 kPa (up to 3000 m above sea level)
Vibration
5g
Gases that may endanger functions according to DIN 40046-36,
DIN 40046-37
Sulfur dioxide (SO
2
)
Concentration 10 ±0.3 ppm
Ambient conditions
- Temperature:
25°C (±2°C)
- Humidity:
75% (±5%)
- Test duration:
10 days
Hydrogen sulfide (H
2
S)
Concentration 1 ±0.3 ppm
Ambient conditions
- Temperature:
25°C (±2°C)
- Humidity:
75% (±5%)
- Test duration:
4 days
Resistance of housing material to termites
Resistant
Resistance of housing material to fungal decay
Resistant
This temperature range is only guaranteed if the Inline controller is mounted horizontally.
Conformance with EMC Directive 2014/30/EU
Noise immunity test according to EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2/
IEC 61000-4-2
Criterion B
6 kV contact discharge
8 kV air discharge
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
Criterion A
Field strength: 10 V/m
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
Criterion B
Supply lines: 2 kV
Signal/data lines: 2 kV
Surge test
EN 61000-4-5
IEC 61000-4-5
Criterion B
Signal/data lines: 1 kV
Supply lines: 0.5 kV
Conducted interference
EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage: 10 V
Noise emission test according to EN 61000-6-4
Class A
NOTE: Radio interference
This is a Class A item of equipment. When using the equipment in residential areas, it may cause radio interference. In this case, the operator
may be required to implement appropriate measures and to pay the resulting costs.
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...