Description of the Inline controller
6959_en_07
PHOENIX CONTACT
37
Terminal
point
Assignment
Remark
Connector 5
Power connector
1.1
24 V
DC
(U
S
)
24 V supply
segment voltage
The supplied voltage is directly routed to the potential jumper.
1.2
24 V
DC
(U
ILC
)
24 V supply
The 7.5 V communications power (U
L
) for the ILC and the connected local bus
devices is generated from this voltage. The 24 V analog voltage (U
ANA
) for the
local bus devices is also generated.
2.1, 2.2
24 V
DC
(U
M
)
24 V main
voltage supply
(main power)
The main voltage is routed to the local bus devices via the potential jumpers.
1.3
LGND
Logic ground
reference
potential
The potential is reference ground for the communications power.
2.3
SGND
Segment ground
reference
potential
The reference potential is directly routed to the potential jumper and is,
simultaneously, reference ground for the main and segment supply.
1.4, 2.4
FE
Functional earth
ground (FE)
Functional earth ground must be connected through the power supply. The
contacts are directly connected to the potential jumper and FE springs on the
bottom of the housing. The Inline controller is grounded when it is snapped
onto a grounded DIN rail. Functional earth ground is only used to discharge
interference.
NOTE:
Protect the supply voltage externally according to the connected
load (local bus devices) with
8 A, maximum
. Make sure the
external fuse blows in the event of an error.
NOTE:
Protect the supply voltage externally according to the connected
load (local bus devices) with
2 A, maximum
. Make sure the
external fuse blows in the event of an error.
NOTE:
Protect the supply voltage externally according to the connected
load (local bus devices) with
8 A, maximum
. Make sure the
external fuse blows in the event of an error.
NOTE:
The
maximum total current
flowing through the potential jumpers is
8 A
.
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...